Installation manual

272313-UIM-A-0407
Unitary Products Group 27
NOTES:
1. Airflow expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m
3
/min).
2. Return air is through side opposite motor (left side).
3. In order to stay within the velocity rating the filters, airflows above 1800 CFM (50.97 m
3
/min) require either return from two sides or one side plus bottom.
4. Motor voltage at 115 V.
5. NR = Operation at this static pressure is not recommended.
FILTER PERFORMANCE
The airflow capacity data published in Table 17 represents blower per-
formance WITHOUT filters. To determine the approximate blower per-
formance of the system, apply the filter drop value for the filter being
used or select an appropriate value from the Table 18.
NOTE: The filter pressure drop values in Table 18 are typical values for
the type of filter listed and should only be used as a guideline. Actual
pressure drop ratings for each filter type vary between filter manufactur-
ers.
TABLE 17:
Blower Performance CFM
Models
Input
Airflow/
Cabinet
Speed
Tap
Airflow with Bottom or One Side Retrun -
without Filters
(CFM)
Airflow with Bottom or One Side Retrun -
without Filters
(m
3
min)
External Static Pressure, Inches W.C. External Static Pressure, Inches (kPa)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 0.025 0.050 0.075 0.099 0.124 0.149 0.174 0.199 0.224 0.249
40/1200/A
High 1395 1330 1265 1200 1120 1030 940 820 NR NR 40 38 36 34 32 29 27 23 NR NR
Med-High 1025 990 960 925 885 825 750 660 NR NR 29 28 27 26 25 23 21 19 NR NR
Med-Low 785 765 745 715 670 625 545 NR NR NR 22 22 21 20 19 18 15 NR NR NR
Low 640 605 590 565 530 465 405 NR NR NR 18 17 17 16 15 13 11 NR NR NR
80/1200/B
60/1200/B
High 1650 1605 1570 1525 1465 1410 1350 1275 1170 1060 47 45 44 43 41 40 38 36 33 30
Med-High 1165 1185 1175 1165 1150 1140 1100 1050 970 875 33 34 33 33 33 32 31 30 27 25
Med-Low 895 915 935 940 940 920 905 860 815 750 25 26 26 27 27 26 26 24 23 21
Low 710 725 725 725 720 700 685 660 625 560 20 21 21 21 20 20 19 19 18 16
100/2000/C
High 2300 2210 2120 2020 1930 1830 1715 1595 1480 1350 65 63 60 57 55 52 49 45 42 39
Med-High 1950 1900 1830 1755 1680 1595 1500 1390 1270 1155 55 54 52 50 48 45 42 39 36 33
Med-Low 1610 1545 1490 1440 1390 1315 1230 1155 1050 920 46 44 42 41 39 37 33 33 30 26
Low 1325 1270 1225 1175 1105 1045 990 905 890 790 38 36 35 33 31 30 28 25 25 22
100/1600/C
80/1600/C
High 1960 1955 1925 1890 1830 1765 1695 1615 1600 1485 56 55 55 54 52 50 48 46 45 42
Med-High 1565 1560 1560 1575 1545 1530 1475 1425 1365 1260 44 44 44 45 44 43 42 40 39 36
Med-Low 1230 1275 1285 1300 1310 1300 1280 1245 1190 1070 35 36 36 37 37 37 36 35 34 30
Low 930 945 965 975 975 975 975 950 910 850 26 27 27 28 28 28 28 27 26 24
120/2000/D
High 2560 2485 2410 2320 2220 2135 2035 1920 1785 1650 72 70 68 66 63 60 58 54 51 47
Med-High 2090 2050 1990 1970 1885 1820 1760 1675 1545 1405 59 58 56 56 53 52 50 47 44 40
Med-Low 1695 1675 1665 1615 1565 1510 1460 1385 1285 1140 48 47 47 46 44 43 41 39 36 32
Low 1175 1150 1135 1110 1085 1055 1005 980 970 845 33 33 32 31 31 30 28 28 27 24
Models
Input
Airflow/
Cabinet
Speed
Tap
Airflow with Two Side Returns or with Bottom and One
Side Return - without Filters
(CFM)
Airflow with Two Side Returns or with Bottom and One
Side Return - without Filters
(m
3
min)
External Static Pressure, Inches W.C. External Static Pressure, Inches (kPa)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 0.025 0.050 0.075 0.099 0.124 0.149 0.174 0.199 0.224 0.249
100/2000/C
HIGH 2465 2380 2295 2195 2095 1995 1875 1760 1620 1470 70 67 65 62 59 56 53 50 46 42
M-HI 2085 2035 1960 1880 1800 1705 1605 1485 1360 1235 59 58 55 54 51 48 45 42 39 35
M-LO 1725 1625 1595 1540 1485 1405 1315 1235 1125 995 49 46 45 44 42 40 37 35 32 28
LOW 1420 1360 1310 1255 1180 1120 1070 970 950 845 40 39 37 36 33 32 30 27 27 24
120/2000/D
HIGH 2615 2535 2450 2385 2285 2175 2075 1945 1825 1670 74 72 69 68 65 62 59 55 52 47
M-HI 2055 2045 2015 1985 1932 1855 1785 1730 1605 1470 58 58 57 56 55 53 51 49 45 42
M-LO 1690 1650 1620 1600 1570 1525 1470 1395 1300 1200 48 47 46 45 44 43 42 40 37 34
LOW 1345 1335 1335 1285 1250 1230 1180 1115 1010 850 38 38 38 36 35 35 33 32 29 24
TABLE 18:
Filter Performance - Pressure Drop Inches W.C. and (kPa)
Airflow Range
Minimum
Opening Size
Filter Type
Disposable Washable Fiber Pleated
CFM
m
3
/min in
2
cm
2
In W.C. kPA In W.C. kPA In W.C. kPA
0 - 750 0 - 21.4 230 1484 0.01 0.00249 0.01 0.00249 0.15 0.03736
751 - 1000 21.25 - 28.32 330 2129 0.05 0.01245 0.05 0.01245 0.20 0.04982
1001 - 1250 28.33 - 35.40 330 2129 0.10 0.02491 0.10 0.02491 0.20 0.04982
1251 - 1500 35.41 - 42.48 330 2129 0.10 0.02491 0.10 0.02491 0.25 0.06227
1501 - 1750 42.49 - 49.55 380 2452 0.15 0.03736 0.14 0.03487 0.30 0.07473
1751 - 2000 49.56 - 56.63 380 2542 0.19 0.04733 0.18 0.04484 0.30 0.07473
2001 & Above 56.64 - Above 463 2987 0.19 0.04733 0.18 0.04484 0.30 0.07473