Installation manual

035-19310-002-B-0504
Unitary Products Group 51
TABLE 39: ELECTRIC HEAT CORRECTION
FACTORS
NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER
208
208 1.00
240
230 0.92
480
460 0.92
600
575 0.92
TABLE 40: VOLTAGE LIMITATIONS
1
1.
Utilization Range “A” in accordance with ARI Standard
110.
POWER SUPPLY
VOLTAGE
MIN. MAX.
208/230-3-60
187 252
460-3-60
432 504
575-3-60
540 630
FIGURE 10 - UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW