TABLE 33: ELECTRICAL DATA - DF060 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
NONE 0.0 0.0 59.0 90
2CE04510506 4.0 19.2 59.0 90
2CE04510706 5.6 26.9 59.0 90
2CE04511006 8.0 38.5 68.8 90
2CE04511506 11.9 57.2 92.3 100
2CE04512006 15.9 76.4 116.3 125
2CE04513006 22.2 106.7 154.2 175
NONE 0.0 0.0 59.0 90
2CE04510506 5.3 22.1 59.0 90
2CE04510706 7.5 31.3 59.8 90
2CE04511006 10.6 44.2 76.0 90
2CE04511506 15.9 66.3 103.6 110
2CE04512006 21.2 88.3 131.2 150
2CE04513006 29.6 123.3 174.9 175
NONE 0.0 0.0 43.0 60
2CE04510525
2
4.0 11.1 43.0 60
2CE04510725
2
5.6 15.5 43.0 60
2CE04511025 8.0 22.2 48.5 60
2CE04511525 11.9 33.0 62.0 70
2CE04512025 15.9 44.1 75.9 80
2CE04513025 22.2 61.6 97.8 100
NONE 0.0 0.0 43.0 60
2CE04510525
2
5.3 12.7 43.0 60
2CE04510725
2
7.5 18.0 43.3 60
2CE04511025 10.6 25.5 52.6 60
2CE04511525 15.9 38.2 68.6 70
2CE04512025 21.2 51.0 84.5 90
2CE04513025 29.6 71.2 109.8 110
NONE 0.0 0.0 21.0 30
2CE04510746
2
6.8 8.2 21.0 30
2CE04511046
2
10.1 12.1 25.6 30
2CE04511546
2
13.6 16.4 30.8 35
2CE04512046
2
19.5 23.5 39.7 40
2CE04513046
2
28.8 34.6 53.7 60
NONE 0.0 0.0 17.6 20
2CE04511058 10.6 10.2 21.0 25
2CE04511558 15.9 15.3 27.4 30
2CE04512058 21.2 20.4 33.8 35
2CE04513058 30.4 29.3 44.9 45
Max Fuse /
BRKR
1
Size
Amps
RLA
Each
LRA
Each
ID Blower
Motor
FLA
Conv
Outlet
Amps
Electric Heater
Model No.
Heater
kW
OD Fan
Motor
FLA
Heater
Amps
Minimum
Circuit
Ampacity
Amps
Model
Tonnage
Voltage
148
5
208-1-60 32.1
230-1-60
Compressors
32.1 148
2.3 6.6
5.0
10.0
2.3 6.6 10.0
1.3
3.3 4.0
460-3-60 9.1 62
575-3-60 7.9 50 1.3
3.3
2.3
10.02.3 6.6
6.6 10.0
230-3-60 19.3 123
208-3-60 19.3 123
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.