TABLE 8: D1EB048 SUPERHEAT CHARGING (IMPERIAL)
OUTDOOR
TEMPERATURE
(°F)
SUPERHEAT AT COMPRESSOR SUCTION (°F)
AIRFLOW = 1,800 CFM
INDOOR WB TEMPERATURE (°F)
55 57 59 61 63 65 67 69 71 73 75
65 19.9 21.0 22.1 23.3 24.4 25.6 26.7 28.0 29.3 30.0 30.7 
70 16.5 17.9 19.2 20.6 22.0 23.4 24.8 26.3 27.8 28.6 29.4 
75 13.1 14.7 16.3 18.0 19.6 21.3 22.9 24.6 26.3 27.2 28.1 
80 9.7 11.6 13.4 15.3 17.2 19.1 21.0 22.9 24.8 25.8 26.8 
85 6.3 8.4 10.5 12.7 14.8 17.0 19.1 21.2 23.3 24.4 25.5 
90 - 5.7  7.8  9.9  11.9 14.0 16.1 18.8 21.5 22.8 24.1 
95 - - 5.0  7.0  9.1  11.1 13.1 16.3 19.6 21.2 22.8 
100 - - - 5.4  6.9  8.5  10.0 13.6 17.3 19.1 20.9 
105 - - - - - 5.9 6.9 11.0 15.0 17.0 19.0 
110 - - - - - - - 8.3 12.6 14.8 17.0 
115 - - - - - - - 5.6 10.3 12.7 15.1 
TABLE 9: D1EB048 SUPERHEAT CHARGING (METRIC)
OUTDOOR
TEMPERATURE
(°C)
SUPERHEAT AT COMPRESSOR SUCTION (°C)
AIRFLOW = 0.85 M
3
/S
INDOOR WB TEMPERATURE (°C)
13 14 15 16 17 18 19 21 22 23 24
18 11.0 11.7 12.3 12.9 13.6 14.2 14.8 15.6 16.3 16.7 17.0 
21 9.1 9.9 10.7 11.5 12.2 13.0 13.8 14.6 15.5 15.9 16.3 
24 7.3 8.2 9.1 10.0 10.9 11.8 12.7 13.7 14.6 15.1 15.6 
27 5.4 6.4 7.5 8.5  9.6  10.6 11.7 12.7 13.8 14.3 14.9 
29 3.5 4.7 5.9 7.0 8.2 9.4 10.6 11.8 13.0 13.6 14.1 
32 - 3.2 4.3 5.5 6.6 7.8 8.9 10.4 11.9 12.7 13.4 
35 - - 2.8 3.9 5.0 6.2 7.3 9.1 10.9 11.8 12.7 
38 - - - 3.0 3.9 4.7 5.6 7.6 9.6 10.6 11.6 
41 - - - - - 3.3 3.9 6.1 8.3 9.4 10.5 
43 -------4.6 7.0 8.2 9.5 
46 -------3.1 5.7 7.1 8.4 