GROUNDING LUG MOUNTING DETAILS:
Details are provided for both the WEEB and Ilsco products. The WEEBLug has a
grounding symbol located on the lug assembly. The Ilsco lug has a green colored
set screw for grounding indication purposes. Installation must be in accordance
with NFPA NEC 70, however the electrical designer of record should refer to the
latest revision of NEC for actual grounding conductor cable size.
Required if not using approved integrated grounding microinveters
WEEBLUG CONDUCTOR - UNIRAC P/N 008002S:
Apply Anti Seize and insert a bolt in the aluminum rail and through the clearance
hole in the stainless steel at washer. Place the stainless steel at washer on the bolt,
oriented so the dimples will contact the aluminum rail. Place the lug portion on the
bolt and stainless steel at washer. Install stainless steel at washer, lock washer and
nut. Tighten the nut until the dimples are completely embedded into the rail and lug.
TORQUE VALUE 10 ft lbs. (See Note on PG. A)
See product data sheet for more details, Model No. WEEB-LUG-6.7
ILSCO LAY-IN LUG CONDUCTOR - UNIRAC P/N 008009P: Alternate Grounding Lug
- Drill and bolt thru both rail walls per table.
TORQUE VALUE 5 ft lbs. (See Note on PG. A)
See product data sheet for more details, Model No. GBL-4DBT.
GROUNDING LUG - BOLT SIZE & DRILL SIZE
GROUND LUG BOLT SIZE DRILL SIZE
WEEBLug 1/4"
N/A - Place in Top SM Rail Slot
IlSCO Lug #10-32 7/32"
• Torque value depends on conductor size.
• See product data sheet for torque value.
STANDARD SYSTEM GROUNDING
I-3
ONLY ONE LUG PER ROW OF MODULES:
Only one lug per row of modules is required.
See Page F for additional lugs required for
expansion joints.