Installation Guide

UNIQUE!24CT/30CT/36CT !
19
Gas Cooktop Conversion and Adjustment Guide
The cooktop is set for use with Liquefied Petroleum (LP). The factory setting is
indicated on the serial plate. When set for Natural Gas (NG) operation, the pressure
regulator will regulate the pressure to 4 inches water column. When set for LP Gas
operation, the pressure regulator will regulate the gas to 10 inches water column
pressure.
LPG to NG Conversion
Convertible Pressure Regulator
The cooktops are shipped to operate on LPG. NG orifices are shipped with the unit
in a separate envelope with the manual. The inlet pressure of the gas supply shall be
in accordance with the nominal inlet pressure of the regulator used on the cooktop
or 1/2 psig maximum. The cooktop should be tested by pressurizing the regulator
with an inlet pressure at least 1 inch water column above the manufacturer's
specified manifold pressure shown on the serial plate.
1. Shut off gas leading to appliance.
2. Unplug any electrical connections if you are using the 110V option, usually
located under the cooktop.
3. Locate convertible regulator under the cooktop, remove cap and pop out the
pin that’s attached.
4. Below you will see the pin positon for use with LPG.
5. Pull out pin and flip it to the NG position see below.
6. Below is an example of both positions.