Service Manual And Spare Parts List And
Contents SAFETY FIRST! ……………………………………………………………... iii 1. INTRODUCTION 1.1. Product Overview ....................................................................................... 1 1.2. Nameplate Information .............................................................................. 2 2. TECHNICAL DATA TABLES 2.1. Technical Data Tables – Models CU-150, CU-200, CU-250 ….……..…3 2.2. Technical Data Tables – Models CU-300, CU-350, CU-400 …………… 7 2.3. Technical Data Tables – Models CU-450, CU-480, CU-500...
7. INSTALLATION INSTRUCTIONS 7.1. General ………………………………..………………………………. 43 7.2. Standard Accessories ………………………..…..…………………….. 43 7.3. Electrical Requirements……………………..…………………………. 43 7.4. Typical System Installation ………………..…….…………………… 44 7.5. Installing the Outdoor Unit ………………..…….…………………… 45 7.6. Installing the Indoor Unit …………………..…….……………………. 46 7.7. Air Duct Installation ………………………..……….…………………... 47 7.8. Connecting the Drain Hose ………………..………..…………………. 48 7.9.
SAFETY FIRST! Safe operation is UNIQUE's number-one priority when designing products. Please read all the safety information and the instructions completely prior to beginning the installation and operation of the unit. UNIQUE products are designed for HVAC use. Using this equipment for any other purpose or in a way not within the operation recommendations specified in this manual will void the warranty and may cause injury.
NOTES ……………………………………………………………………………………………………………………… ……………………………………………………………………………………………………………………… ……………………………………………………………………………………………………………………… ……………………………………………………………………………………………………………………… ……………………………………………………………………………………………………………………… ……………………………………………………………………………………………………………………… ……………………………………………………………………………………………………………………… ……………………………………………………………………………………………………………………… ……………………………………………………………………………………………………………………… ……………………………………………………………………………………………………………………… ………………………………………………………………………………………………………………………
1. INTRODUCTION This Service Manual has been prepared as an aid to HVAC installation teams and users, to help you better understand the equipment. This information is also designed to make you aware that the Air Conditioner is a product that must be used with care and understanding. This Service Manual provides comprehensive technical documentation for all models of UNIQUE-CU split and packaged air conditioners.
1.3 Nameplate Information Technical information for a specific unit appears on the unit nameplate, which is attached to the indoor and/or the outdoor units. The unit nameplate includes the following information: MODEL Air-conditioner model name SERIAL NUMBER Serial Number of the unit. CLIMATE CLASS Class T1 – Standard conditions. VOLT/PHASE/Hz A/C power supply, for example: 400/3/50 = 400V/3 Phase/50 Hz. COS φ Power factor for the unit. FUSE Required fuse size, Amp.
2.1 Technical data table – Models CU150, CU200, CU250 2.1.1 Performance R22 Model Cooling capacity Heating capacity Power Consumption - cooling CU150 CU200 CU250 Watt 4430 5569 7181 Btu/h 15100 19000 24500 Watt 4580 5715 7386 Btu/h 15280 19500 25200 Watt 1670 2135 2695 Power Consumption - Heating Watt 1520 1905 2460 Operating Current (cooling/Heating) Amp 7.9/7.2 10.1/9.5 12.7/11.6 E.E.R - Energy Efficiency Ratio Cooling 9.0 8.9 9.1 C.O.
2.1.2 Outdoor Unit Data – Models CU150, CU200, CU250 Model CU150 Casing color CU200 CU250 RAL 7032 RAL 7032 RAL 7032 mm 900x380x585 900x380x585 900x380x585 m /h 3 2465 3230 3400 cfm 1450 1900 2000 Noise Level (see note 1) dbA 44 46 46 Fittings Type Dimensions (LxDxH) Air flow (at high speed) Flare Flare Flare Capillary Tube Capillary Tube Capillary Tube mm 500/1 500/1 500/1 KW 0.15 0.15 0.15 µF/Volt 5/400 5/400 5/400 R.P.
2.1.3 Indoor Unit Data - Models CU150, CU200, CU250 Indoor Unit Dimensions (LxDxH) Supply Air Duct Dim. (A, B, C) Return Air Duct Dim.
NOTES ................................................................................................................................................................... ................................................................................................................................................................... ................................................................................................................................................................... ..............
2.2 Technical data table – Models CU300, CU350, CU400 2.2.1 Performance R22 Model Cooling capacity CU300 CU350 CU400 Watt 8734 9965 11284 Btu/h 29800 34000 38500 Watt 8792 10111 11430 Btu/h 30000 34500 39000 Power Consumption - cooling Watt 3240 3470 4410 Power Consumption – Heating Watt 2750 3260 4155 Operating Current (cooling/Heating) Amp 15.3/14.5 17.6/16.6 20.8/19.6 E.E.R – Energy Efficiency Ratio Cooling 9.2 9.8 8.7 C.O.
2.2.2 Outdoor Unit Data – Models CU300, CU350, CU400 Model CU300 Casing color CU350 CU400 RAL 7032 RAL 7032 RAL 7032 mm 1080x380x585 1080x380x585 1080x380x585 m /h 3 3910 3910 4250 cfm 2300 2300 2500 Noise Level (see note 1) dbA 46 46 47 Fittings Type Dimensions (LxDxH) Air flow (at high speed) Flare Flare Flare Capillary Tube Capillary Tube Capillary Tube mm 500/1 500/1 500/1 KW 0.15 0.15 0.15 µF/Volt 5/400 5/400 5/400 Expansion Device Axial Fan Diameter/No.
2.2.3 Indoor Unit Data - Models CU300, CU350, CU400 Indoor Unit Dimensions (LxDxH) Supply Air Duct Dim. (A, B, C) Return Air Duct Dim.
NOTES ................................................................................................................................................................... ................................................................................................................................................................... ................................................................................................................................................................... ..............
2.3 Technical data table – Models CU450, CU480, CU500 2.3.1 Performance R22 Model Cooling capacity CU450 CU480 CU500 Watt 13189 14009 14654 Btu/h 45000 47800 50000 Watt 13335 14185 15533 Btu/h 45500 48400 53000 Power Consumption - cooling Watt 5060 5400 5730 Power Consumption - Heating Watt 4760 5000 5350 Operating Current (cooling/Heating) See note 3 Amp 8.5/8.4 8.9/8.4 9.6/9.0 E.E.R - Energy Efficiency Ratio Cooling 8.9 8.85 8.7 C.O.
2.3.2 Outdoor Unit Data – Models CU450, CU480, CU500 Model CU450 Casing color CU480 CU500 RAL 7032 RAL 7032 RAL 7032 mm 1150x415x661 1150x415x661 1150x415x661 m /h 3 4760 5100 5780 cfm 2800 3000 3400 Noise Level (see note 1) dbA 47 48 50 Fittings Type Dimensions (LxDxH) Air flow (at high speed) Flare Flare Flare Capillary Tube Capillary Tube Capillary Tube mm 500/1 500/1 550/1 KW 0.15 0.15 0.37 µF/Volt 5/400 5/400 10/400 R.P.
2.3.3 Indoor Unit Data - Models CU450, CU480, CU500 Indoor Unit Dimensions (LxDxH) Supply Air Duct Dim. (A, B, C) Return Air Duct Dim.
NOTES ................................................................................................................................................................... ................................................................................................................................................................... ................................................................................................................................................................... ..............
2.4 Technical data table – Models CU600, CU700, CU800 2.4.1 Performance R22 Model Cooling capacity CU600 CU700 CU800 Watt 17585 21102 24619 Btu/h 60000 72000 84000 Watt 17790 21249 24912 Btu/h 60700 72500 85000 Power Consumption - cooling Watt 7700 9500 10000 Power Consumption - Heating Watt 7100 8000 9500 Operating Current (cooling/Heating) See note 3 Amp 12.9/11.9 16.0/13.4 16.8/16.0 E.E.R - Energy Efficiency Ratio Cooling 7.8 7.6 8.4 C.O.
2.4.2 Outdoor Unit Data – Models CU600, CU700, CU800 Model Casing color Dimensions (LxDxH) mm CU600 CU700 CU800 RAL 7032 RAL 7032 RAL 7032 1650x500x730 1650x500x730 1650x500x830 3 m /h 8500 10200 11900 cfm 5000 6000 7000 Noise Level (see note 1) dbA 52 54 54 Fittings Type Flare Flare Flare Air flow (at high speed) Expansion Device Axial Fan Capillary tube or expansion valve Diameter/No. mm 500/2 550/2 550/2 KW 0.15 0.37 0.
2.4.3 Indoor Unit Data - Models CU600, CU700, CU800 Indoor Unit Dimensions (LxDxH) Supply Air Duct Dim. (A, B, C) Return Air Duct Dim.
NOTES ................................................................................................................................................................... ................................................................................................................................................................... ................................................................................................................................................................... ..............
2.5 Technical data table – Models CU1000, CU1200, CU1400 2.5.1 Performance R22 Model Cooling capacity CU1000 CU1200 CU1400 Watt 28341 35258 42204 Btu/h 96700 120300 144000 Watt 28517 35610 42614 Btu/h 97300 121500 145400 Power Consumption - cooling Watt 11500 14000 17000 Power Consumption - Heating Watt 11000 13300 16100 Operating Current (cooling/Heating) See note 3 Amp 19.3/18.5 23.5/22.3 28.6/27.1 E.E.R - Energy Efficiency Ratio Cooling 8.4 8.6 8.47 C.O.
2.5.2 Outdoor Unit Data – Models CU1000, CU1200, CU1400 Model CU1000 CU1200 CU1400 RAL 7032 RAL 7032 RAL 7032 1700x830x1000 1700x830x1000 1700x830x1150 m /h 16150 15300 15300 cfm 9500 9000 9000 Casing color Dimensions (LxDxH) mm 3 Air flow (at high speed) Noise Level (see note 1) dbA 75 75 75 Fittings Type Flare Soldering Soldering Expansion valve Expansion valve Expansion valve Expansion Device Axial Fan Diameter/No. mm 630/2 630/2 630/2 KW 2x0.66 2x0.66 2x0.
2.5.3 Indoor Unit Data - Models CU1000, CU1200, CU1400 Indoor Unit Dimensions (LxDxH) Supply Air Duct Dim. (A, B, C) Return Air Duct Dim. (WidexHigh) High Fan Speed (Number of Speeds) Air Flow (at High speed) CU1000-A CU1000-C CU1200-A CU1400-A mm 1500x700x480 1300x800x580 1600x800x550 1600x800x660 mm 295, 335, 970 345, 400 345, 400, 1190 345, 400, 1190 mm 1300x457 1065x560 1400x533 1400x635 R.P.
NOTES ................................................................................................................................................................... ................................................................................................................................................................... ................................................................................................................................................................... ..............
3. CU Series Packaged Units Designed for outdoor installation, UNIQUE CU Packaged Units (designated CUP) feature eleven sizes of self contained, pre assembled and fully wired air conditioners.
3.1 Packages CUP350…CUP500 3.1.1 Performance Notes: 1. Nominal cooling capacity based on indoor air temp. 27ºC db/19.5ºC wb and outdoor air temp. 35ºC db/24º wb. 2. Nominal heating capacity based on indoor air temp. 21ºC db and outdoor air temp. 7.5ºC db/6.1ºC wb. 3. Operating current models CUP350 and CUP400: for 230V, 1Ph. Operating current models CUP450…CUP500 measured at the most loaded phase.
3.1.2 Technical Data Model CUP350 CUP400 CUP450 CUP480 CUP500 GENERAL LxDxH mm 1080x1100x850 1080x1100x850 1200x1100x850 1200x1100x850 1200x1150x1030 A mm 265 265 265 265 295 B mm 305 305 305 340 335 E mm 380 380 380 380 460 F mm 555 655 755 755 785 Condensate Lines - Drain Ф-mm (in) 19 (3/4") 19 (3/4") 19 (3/4") 19 (3/4") 19 (3/4") Noise Level (see note 1) dbA 46 47 47 48 50 Net Weight Kg.
3.2 Packages CUP600…CUP800 3.2.1 Performance Notes: 1. Nominal cooling capacity based on indoor air temp. 27ºC db/19.5ºC wb and outdoor air temp. 35ºC db/24º wb. 2. Nominal heating capacity based on indoor air temp. 21ºC db and outdoor air temp. 7.5ºC db/6.1ºC wb. 3. Operating current measured at the most loaded phase.
3.2.2 Technical Data Model CUP600 CUP700 CUP800 GENERAL LxDxH mm 1650x1150x1030 1650x1350x1130 1650x1350x1130 A mm 295 345 345 B mm 335 400 400 E mm 460 510 510 F mm 885 915 1058 Condensate Lines - Drain Ф-mm (in) 22 (7/8") 22 (7/8") 22 (7/8") Noise Level (see note 1) dbA 52 54 54 Net Weight Kg. 260 280 305 Dimensions CONDENSER SIDE Air flow (at high speed) Axial Fan Diameter m /h 3 8500 10200 11900 cfm 5000 6000 7000 mm 500 550 550 2 2 2 R.P.
3.3 Packages CUP1000…CUP1400 3.3.1 Performance Notes: 1. Nominal cooling capacity based on indoor air temp. 27ºC db/19.5ºC wb and outdoor air temp. 35ºC db/24º wb. 2. Nominal heating capacity based on indoor air temp. 21ºC db and outdoor air temp. 7.5ºC db/6.1ºC wb. 3. Operating current measured at the most loaded phase.
3.3.2 Technical Data Model CUP1000 CUP1200 CUP1400 GENERAL LxDxH mm 1700x1500x1150 1700x1500x1150 1700x1500x1250 A mm 295 345 345 B mm 335 400 400 C mm 1010 1114 1114 E mm 460 533 635 Dimensions mm 1335 1435 1435 Condensate Lines - Drain F Ф-mm (in) 28 (1⅛") 28 (1⅛") 28 (1⅛") Noise Level (see note 1) dbA 75 75 75 Net Weight Kg.
NOTES ................................................................................................................................................................... ................................................................................................................................................................... ................................................................................................................................................................... ..............
4.
4.2 Accessories Options Chart 150-350 MODEL 400-500 600-800 High Pressure Control Optional Optional • High/Low Pressure Switch Optional Optional Optional H.G.B.P (Hot Gas By-Pass) Optional Optional Optional Optional • • • • • • Optional Optional Optional Optional (see note) Optional (see note) Optional (see note) • • • ITEM Suction Accumulator Expansion Device Capillary Tube Thermal Exp.
5.
5.
5.
5.
5.
NOTES ................................................................................................................................................................... ................................................................................................................................................................... ................................................................................................................................................................... ..............
6.
6.
6.
6.
7. INSTALATION INSTRUCTIONS 7.1 General All parts and accessories are packed and shipped with appropriate measure to ensure that everything is protected during transportation. The installation team must be familiar with the installation requirements, to exercise due care in handling and to prevent damage to the equipment. The following instructions are in addition to and conform to any state and municipal regulations which may apply.
7.4 Typical CU Split System Installation Fig. 7-2 1. Outdoor Unit (Condenser). 2. Indoor Unit (Evaporator). 3. Duct System. 4. Wall Air Diffusers. 5. Ceiling Air Diffusers. 6. Return Air Door Grill. 7. Return Air Intake Grill. 8. Control Unit. 9. Inter-Unit Piping and Wiring. 7.4.1 Indoor and Outdoor Unit Location The indoor and outdoor units should be installed as close to each other as possible. Do not exceed the tubing length and height differences as shown in the accompanying table. See Fig.
7.5 Installing the Outdoor Unit • • • • • • • • • • Make sure to leave sufficient space around the unit. See figure 7-4 for minimum required distance between the unit and nearby walls. Install the unit in a location with convenient access for service and maintenance purposes. Protect the unit from any heat source. Prevent from any dust or strong wind installation sites. Position the unit in such a way to minimize motor noise which reaches the user and neighbors. The unit must be installed at least 5 cm.
7.6 Installing the Indoor Unit AB SOR BTION CUSHION AB SOR BTION CUSHION LONG C EILING ANC HOR S LONG C EILING ANC HOR S Fig. 7-5 • • • • • Overall and duct connecting dimensions are shown in the technical data tables. Allow free access to the service door, air filter and control box. Carefully plan the drainage tube path at a minimum slope of 2% avoiding sharp bends or oil traps. The indoor unit may be installed either hanging from the ceiling or resting on hard surface (i.e. concrete).
7.6.3 Drilling a Hole in the Wall for Drainage and Inter-Unit Connections • • • • To make the connections between the indoor and outdoor units, a 70 mm hole should be drilled for the refrigerant lines, drainage hose and electrical cable passage, through the wall, as shown in Figure 7-6. Make sure to drill outwards and downwards, so that the opening in the outside wall is at least 10 mm lower than the opening on the inside. Route the drainage hose at the bottom of the hole.
7.8 Connecting the Drain Hose Connect the rubber syphon to the drain hose connection. See Fig. 7-8 for details. Fig. 7-8 7.9 Connecting the Refrigerant Lines and Refrigerant Charge 7.9.1 Connecting the Refrigerant Lines • • • • • • Use tubing sizes according to the following table. To connect the refrigerant lines use only "L" type sealed, dehydrated copper refrigerant tubing. No other type may be used. The use of other types of tubing will void the manufacturer's warranty.
7.9.2 Flaring and Connecting • • • • • Remove the protecting cap from the flare fitting. Remove the protecting cap from the tubing and cut to the required length. Make sure that the cut is perpendicular and clean, without burrs. Slip the flare nut on the tubing and flare the tube end, using standard flaring tools. Tighten the nut until resistance is met. Using a suitable wrench, tighten an additional 1/4 turn. Use the following specified torque, according to connection size. See illustration in Fig.7-9.
Tubing Line 3/8"-1/2" 3/8"-5/8" 1/2"-5/8" 1/2"-3/4" 1/2"-7/8" 5/8"-7/8" 5/8"-1⅛" 3/4"-1⅜" Add refrigerant and oil if tubing exceeds 10 m. For each 1 m. tubing add: Refrigerant (gr.) Oil (gr.
8. INSTALLING THE CONTROL SYSTEM AND CONNECTING POWER 8.1 Identification of the Components MIG 101: Main control box. Standard supply for all units. M101P: I/R (Infra Red) Receiver Panel, wall mounted. Features I/R receiving and On/Off pushbuttons. Standard supply for all units that do not have the wall mounted thermostat ETN1000. L3 L2 L1 N N C RV F1 F2 N H I ME L O 14 15 16 17 T1 T1 T2 T2 T3 T3 RT-01: I/R Transmitter (Remote Control). Daily programmable. IRR/1: I/R Room Receiver, wall mounted.
8.2 Installing the Wall Mounted Units and the Remote Control • • • • • Remove all control components from their packaging. Place the control box on the indoor unit service door, or up to 1.5 m. from the unit. The box should be conveniently located for access by service personnel. Protect both the control box and the electrical connections from water and high humidity. Install the in-room wall mounted units.
- 53 -
- 54 -
8.
8.5 Wiring the Outdoor Unit • • • • • • • Locate the terminal box cover according to the following figures. Remove the outdoor unit side cover. Connect the wires to the terminals, in accordance with the color coding and the suitable wiring diagrams. Connect the outdoor sensor cable, making sure the connector is properly inserted. Secure the inter-unit electrical cable to the outdoor unit using the clamps. Make sure that all screws and wires are properly fastened.
8.5.3 Outdoor Unit Terminal Box CUC-600…800 8.5.
8.6 Wiring the Indoor Unit • • • • • • Locate the terminal box cover according to the following figures. Remove the indoor unit side cover. Connect the wires to the terminals, in accordance with the color coding and the suitable wiring diagrams. Make sure that all connections are properly inserted and fastened. Make sure that all screws and wires are properly fastened. Loose wires or connections can cause damage and present a fire hazard! Reassemble the side cover. 8.6.
8.6.2 Indoor Unit Terminal Box CUE-1000A…1400A BROWN 8.7 Finishing the Job • • • • • • Hide the tubing wherever possible. Make sure that the drainage tube slopes downstream along its entire length. Insulate tubing connections with insulation materials. Fasten tubes to the outside wall. Seal the hole through which the cables and tubing are passing. Connect the air conditioner to the power source. Check all air conditioning operating modes. Consult the user manual. 8.7.
9. TROUBLESHOOTING GUIDE 9.1 General Troubleshooting. Note: Check for broken wires and loose cable lugs first! Warning: Always unplug the A/C before performing cleaning or maintenance activities. Symptom 1 2 3 A/C fails to start. Only indoor fan ventilator works although cooling or heating is desired. Only indoor fan motor and compressor working. Outdoor fan motor stopped. Probable Cause Corrective Action 1. Power supply to unit not connected (LCD display is blank). 1.
General Troubleshooting (continued). Symptom 4 5 Probable Cause In Cool mode: high pressure, or; In Heat mode: outdoor coil freeze. 1. Run capacitor of outdoor fan motor is burnt. 1. Replace outdoor fan motor run capacitor. 2. Winding of outdoor fan motor is shorted. 2. Replace outdoor fan motor. Only indoor fan motor and outdoor fan motor are working. No cooling and/or heating take place. 1. Overload safety device on compressor is cut out due to high temperature. 1.
General Troubleshooting (continued). Symptom Corrective Action Drain pan pipe or hose is clogged or the spout of drain pan is clogged. Disassemble plastic drain-pipe from spout of evaporator drain pan. Flush with clean water. 10 Water dripping Water drain outlet or the spout is clogged. Open condenser cover, clean out water outlet, and clean the base inside thoroughly. 11 Indoor fan is not 1. Failure in motor capacitor. 1. Replace the capacitor. 2. No voltage out of P.C.B. assembly for fan motor.
9.2 Poor Cooling Troubleshooting. Symptom 1 Refrigerant flow failure Probable Cause Corrective Action 1. Refrigerant gas shortage. 1. Charge refrigerant gas. 2. Excessive overcharging of refrigerant. 2. Recharge gas. 3. Gas leakage. 3. Repair leakage. 4. Clogging of strainer or capillary tube. 4. Replace strainer. 5. 4-Way valve is defective. 5. Replace 4-Way valve. 6. Solenoid 4-Way valve is defective. 6. Replace solenoid. 7. Compressor is defective. 7. Replace compressor. 8.
9.3 Poor Heating Troubleshooting. Symptom 1 Refrigerant flow failure Probable Cause Corrective Action 1. Charge refrigerant gas. 1. Refrigerant gas shortage. 2. Recharge gas. 2. Excessive overcharging of refrigerant. 3. Repair leakage. 3. Gas leakage. 4. Replace strainer. 4. Clogging of strainer or capillary tube. 5. Replace 4-Way valve. 5. 4-Way valve is defective. 6. Replace solenoid. 6. Solenoid 4-Way valve is defective. 7. Replace compressor. 7. Compressor is defective. 8. Open the valves full. 8.
10. OPERATING INSTRUCTIONS 10.1. Operating Instructions - RT – 01 - Infra Red Remote Control Transmitter Important Note: The infra red remote control must be directly aimed at the thermostat (or receiver) in order to operate. The thermostat "beeps" every time it has received new information. If no button is pressed for 10 seconds, the display will return to normal display mode. The icon of a selected feature turns dark. Not selected feature remains pale.
Real Time Clock: Press SELECT button: CLOCK SET will flash. Press (+) or (-) buttons, the hours will flash. Use the set button, press (+) to increase and (-) to decrease the hours. Press SELECT button again, the minutes will flash. Use the set button, press (+) to increase and (-) to decrease the minutes. Press SELECT button again to exit from the program or press ON/SEND button to send the information to the thermostat.
10.2. Operating Instructions – M101P M101P is a wall mounted Infra Red Receiver. On/Off Press On/Off button to start or to stop the air conditioner. Can be used when the remote control transmitter is not available. The air conditioner starts at its last preset position. On LED Lights when A/C unit is activated. Timer LED Lights when ON\OFF Timer is activated.
10.3. Operating Instructions – ETN1000 On/Off Press ON/OFF button to activate the thermostat; ON led will lit. For OFF press ON/OFF again; OFF led will lit. Set Temperature Press (+) or (-) button. Temperature digit will flash. Set to the desired temperature using the (+) or (-) buttons. Mode Press MODE button and adjust between: COOL, HEAT, COOL/HEAT (Automatic cool/heat change over) or FAN (fan only).
10.4. Operating Instructions for Wall Mounted Thermostat MIGA2400 10.4.1 General Settings ON/OFF Press ON/OFF button to activate the thermostat. Green led will light. For OFF press again (the green led will flash when compressor time delay protection is ON). MODE Press the MODE button to switch between 4 modes: FAN (Fan only), COOL, HEAT, and HEAT/COOL (automatic Heat\cool change-over).
FAN Fan Only - When only ventilation needed. COOL/HEAT Activate Heating and Cooling automatically according to the difference between the “Set” and “Actual” temperature. COOL Cooling for summer time. Up to 3 stages of cooling can be selected. Cooling stages will be indicated by lines near the cooling icon. HEAT Heating for winter time. Up to 4 stages of heating can be selected. Heating stages will be indicated by lines near the heating icon.
REAL TIME CLOCK Hours adjustment: press CLOCK button, hours digits will flash, using the set button press (+) to increase and (-) to decrease the hours. Minutes adjustment: press CLOCK button again and adjust the minutes. Press CLOCK again to return to normal display mode. TIMER TIMER setting allows you to stop the Air conditioner in a certain time (when it's ON) or to start at certain time (when it's OFF).
10.4.2 PROGRAMMING Two programs are available for setting each week day, Monday – Friday. Another two programs are available for Saturday and another two for Sunday. Monday to Friday programming Press PROG. The display will flash. A. First Program - Start Time: Press PROG. Hours indication will flash. Use the set button to adjust the hours. Press PROG. Minutes indication will flash. Use the set button to adjust the minutes. Stop Time: Press PROG. Hours indication will flash.
Quick Review Mode Enter into programming mode by pressing the PROG. button. Press CLOCK button to advance Mon-Fri, Sat, Sun and out. During this procedure presetting can be reviewed and modified. Switching between Manual and Program operation While unit is on (green ON led lights) press and hold down for 3 seconds the PROG. button. While in PROG. mode On/Off button switches from Manual to Program operation. Timer Override While in Program operation, any remote control timer settings will be override.
NOTES ................................................................................................................................................................... ................................................................................................................................................................... ................................................................................................................................................................... ..............
11. SPARE PARTS LIST 11.
CU150, CU200, CU200 (Outdoor Unit Refrigerant System Components) No. in Figure 1b 1b 4 8 9 10 11 12b Part Description Compressor Compressor 4 Way Solenoid Valve Muffler Refrigerant Filling Valve 3 Way Service Valve 3 Way Service Valve Condenser Heat Exchanger Parts No.
CU600, CU700, CU800 (Outdoor Unit Refrigerant System Components) No. in Figure 1c 1c 1b 2 4 5 6 7 8 9 10 11 12b Parts No.
11.
No. in Figure 1a 2 4 5 7 CU150, CU200, CU250 (Outdoor Unit Electrical Components) Part No. Part Description CU150 CU200 Axial Fan 0404O500 0404O500 Fan motor 03015010 03015010 Fan motor capacitor 100305MF 100305MF Compressor capacitor 100325MF 100335MF Contactor 1001G7LO 1001G7LO CU250 0404O500 03015010 100305MF 100345MF 1001G7LO No. in Figure 1a 2 3 4 5 6 7 CU300, CU350, CU400 (Outdoor Unit Electrical Components) Part No.
No. in Figure 1b 6 7 8 9 CU1000, CU1200, CU1400 (Outdoor Unit Electrical Components) Part No.
11.
Indoor Unit Assembly Parts No. in Fig. 1 2 3 4 Part Description Qty. Per Unit Centrifugal Fan – Impeller (CU -A) Centrifugal Fan – Casing (CU -A) Centrifugal Fan – Right (CU -C) Centrifugal Fan – Left (CU -C) Part No.
Indoor Unit Assembly Parts No. in Fig. 1 2 3 4 Part Description Qty. Per Unit Centrifugal Fan – Right (CU -A) Centrifugal Fan – Left (CU -A) Centrifugal Fan – Right (CU -C) Centrifugal Fan – Left (CU -C) Part No.
Indoor Unit Assembly Parts No. in Fig. 1 2 3 4 Part Description Centrifugal Fan – Right (CU -A) Centrifugal Fan – Left (CU -A) Centrifugal Fan – Right (CU -C) Centrifugal Fan – Left (CU -C) Qty. Per Unit CU1000-A CU1000-C CU1200-A CU1400-A 1 4021108 N/A 4021138 4021120 1 4021109 N/A 4021138 4021120 N/A 4021120 N/A N/A N/A 4021120 N/A N/A Part No.
Appendix A – Additional CU Options Unique’s line of advanced CU air conditioners offers a broad range of configurations. Customized configurations are also available upon request. Outdoor Condensing Units Model Features CUC-DT Suitable for locations where air cannot be directed sideways. Includes two heat exchanger coils. Fan faces upwards. CUC-CT Suitable for locations where air cannot be directed sideways. Includes one heat exchanger coil. Fan faces upwards.
Model Features CUC-VAF Suitable for locations where condensing unit cannot be placed on floor, but can be placed above floor level. Includes two fans, front air discharge. CUC-SQF Extra silent unit. Includes three low speed fans and enlarged heat exchanger.
Indoor Evaporating Units Model CUE-B CUE-D Features Suitable for visible, indoor installations. Air distributed through front side shutters. Prepainted cabinet, available in wide range of colors. Evaporator with two side heat exchangers and one fan between them. Back side of evaporator can be installed next to wall. CUE-AD Evaporator with one heat exchanger and two fans, pushing air sideways. CUE-AVF Narrow, vertical evaporator. Front air suction with dual fan. Front air discharge.
Model CUE-AVTS Features Vertical evaporator. Free bottom side air suction with dual fan. The air is discharged from top side, through heat exchanger. CUE-CVF Narrow, vertical evaporator. Front air suction and front air discharge. CUE-CVT Narrow, vertical evaporator. Front air suction and top side air discharge. CUE-CVFS Vertical evaporator. Free bottom side air suction. Front air discharge, through heat exchanger. CUE-CVTS Vertical evaporator. Free bottom side air suction.
Package Units Model Features CUP-A-350 to 500 Dual Fan configuration for models 350 to 500. CUP-A-600 to 800 Dual Fan configuration for models 600 to 800. CUP-AB Return air suction at upper part of front side. Dual fan air distribution at lower part of front side. CUP-CB Return air suction at upper part of front side. Single fan air distribution at lower part of front side. CUP-AF Standard configuration, with dual fan front air discharge.
Model Features CUP-AT Front side air suction, with dual fan top air discharge. CUP-CT Front side air suction, with single fan top air discharge.
APPENDIX B – Special Control Boards The standard CU Series air conditioners are equipped with MIG 101/3/02 control board. Additional control boards, to suit various climate conditions or special control requirements, are available upon request. See control package features in the following table. Designation MIG 101/3/02 MIG 101/2 MIG 101/1H1 MIG 101/H1 Description Standard control unit. Heat Pump features: 1-stage Cooling and 1- stage Heating.
Designation MIG 101/1H2 Description Heat Pump features: 1-stage Cooling and 2-stage Heating. Additional (3rd stage) heating by electrical heating element, attached to the indoor evaporator's coil. Heat Pump features: 1-stage Cooling and 1-stage Heating. Additional 2 heating stages (2nd and 3rd stage) by electrical heating element, attached to the indoor evaporator's coil. MIG An external thermostat, set point 101/1H2/BEL controlled, monitors the ambient temperature.
- 93 -
- 94 -
- 95 -
- 96 -
- 97 -
- 98 -
- 99 -
NOTES ................................................................................................................................................................... ................................................................................................................................................................... ................................................................................................................................................................... ..............
Unique – Engineering & Air Conditioning Moshav Nehalim 84 P.O.B. 142 Nehalim 49950, ISRAEL Tel. 972-3-9087555, Fax. 972-3-9087444 http://www. unique-eng.co.il e-mail: unique@unique-eng.co.