User's Manual
Chapter 4 Commissioning
4.4 Commissioning Procedure
Duri
ng the commissioning (initial turn-on) procedure, the operator will be required to
perform the following tasks:
1. Power-on the repeater
2. Configure the repeater
3. Place the repeater in broadcast mode
4.4.1 Repeater AC/DC Power-on
NOTE: The
rep
eater is divided into separate LB and HB cabinets. However, there are several
components which are shared by both cabinets, but are physically located in only one of the
cabinets. In this case, the user will be required to move back and forth between cabinets
when powering on the DRU-2KW.
The DRU-2KW AC/DC power should be turned on in the following sequence:
1. Ensure that the BMS front panel DC breakers are switched OFF.
2. Ensure that the BMS rear panel battery breaker BAT CB is switched OFF.
3. Ensure that the control cabinet PDU AC circuit breakers are switched OFF.
4. Ensure that the HB HPA cabinet PDU AC circuit breakers are switched OFF.
5. Ensure that the LB HPA cabinet PDU AC circuit breakers are switched OFF.
6. Switch ON the HBE rear panel DC breaker.
7. Switch ON the LBE rear panel DC breaker.
8. Switch ON the TRMS rear panel AC breaker.
9. Switch ON the Main AC repeater circuit breaker(s), located in the building/site
electrical service panel.
10. Switch ON the AC disconnect device(s), located on or near the repeater (where
applicable).
11. Switch ON the control cabinet PDU MAIN AC (L1 L2) circuit breaker.
12. Switch ON the HB HPA cabinet PDU MAIN1 AC (L1 L2 L3) circuit breaker.
13. Switch ON the HB HPA cabinet PDU MAIN2 AC (L1 L2 L3) circuit breaker.
14. Switch ON the LB HPA cabinet PDU MAIN1 AC (L1 L2 L3) circuit breaker.
15. Switch ON the LB HPA cabinet PDU MAIN2 AC (L1 L2 L3) circuit breaker.
16. Switch ON the 12V battery circuit breaker (BAT CB), located on the BMS rear panel.
17. Switch ON the AC SERVICE circuit breaker (CB3), located on the control cabinet PDU.
18. Switch ON the BMS circuit breaker (CB2), located on the control cabinet PDU.
o Ensure that the 12 VDC rectifier LEDs are illuminated green and that the internal
fans are rotating continuously.
o Ensure that the BMS mounting shelf CTR LED is illuminated green.
SX03-30000-01-M01
4-2