User's Manual

Chapter 3 Installation
3.15 AC Power
3.15.1 General Requirements
A cert
if
ied Electrician should connect the repeater to the building/site electrical service panel
to meet all local and national electrical codes, and according to the repeater electrical
drawing(s).
AC Supply Voltage
o Control Cabinet: 208-240 VAC nominal, Single Phase, 4 wire (L1, L2, N, G)
o HB HPA Cabinet: 208-240 VAC nominal, 3-Phase, 5 wire Delta or Y (L1, L2,
L3, N, G)
o LB HPA Cabinet: 208-240 VAC nominal, 3-Phase, 5 wire Delta or Y (L1, L2,
L3, N, G)
Frequency: 60 Hz
Branch Protection
o The control cabinet is to be installed with a branch protection of 15 A max
o The HB HPA cabinet is to be installed with a branch protection of 70 A max
o The LB HPA cabinet is to be installed with a branch protection of 70 A max
Power Consumption:
o Control Cabinet Current: 10A (Power Consumption: 2.0 kVA max)
o HB Cabinet Current: 47A (Power Consumption: 17 kVA max)
o LB Cabinet Current: 47A (Power Consumption: 17 kVA max)
o Overall: 104A (Power Consumption: 36.0 kVA max
Minimum AC mains wire requirements for the control cabinet:
o Ground Conductor: #8 AWG
o Power Cable (L1, L2, N, G): #12 AWG
o Temperature rating: 75C
Minimum AC mains wire requirements for each HPA cabinet:
o Ground Conductor: #8 AWG
o Power Cable (L1, L2, L3, G): #4 AWG
o Temperature rating: 75C
Verify that the AC supply voltage is within the specified range and check
all power cables for damage.