User's Manual
Table Of Contents
- 1.0 INTRODUCTION
- 2.0 FEATURES & OPTIONS
- 3.0 SAFETY WARNINGS
- 4.0 WARRANTY (summary)
- 5.0 UNPACKING AND INSPECTION
- 6.0 GENERAL SPECIFICATIONS
- 7.0 PRINCIPAL OF OPERATION
- 8.0 FRONT PANEL DESCRIPTION
- 9.0 REAR PANEL DESCRIPTION
- 10.0 LED Indicators
- 11.0 MAKING CONNECTIONS TO THE X75
- 12.0 INSTALLATION
- 13.0 USING THE CONTROLLER WEB BROWSER INTERFACE
- Appendix 1 – SNMPv3 MIB Information
- Appendix 2 – Load LVD (special order)
- Appendix 3 – Revision History
- Figure 1 - X75 Compact Integrated DC Power System
- Figure 2 - Block Schematic
- Figure 3a - Front View with Breakers (configuration A)
- Figure 3b - Front View with GMT Fuses (configuration B)
- Figure 4 - Rear Views of Base and Expansion Units
- Figure 5 - LED Indicators
- Figure 6 - Recommended Load Circuit Wire Sizes
- Figure 7 - Battery Temp. Probe & Alarm Relay Connector Pin-Out
- Figure 8 - Ethernet Connector Pin-Out
- Figure 9 - Auxiliary Connector Pin-Out
- Figure 10 - Input Current Ratings
- Figure 11 - Status WEB Page (typical)
- Figure 12 - Rectifier Status WEB Applet (typical)
- Figure 13 - Installation WEB Applet - system tab (typical)
- Figure 14 - Installation WEB Applet - float & tc tab (typical)
- Figure 15 - Installation WEB Applet - battery tab (typical)
- Figure 16 - Installation WEB Applet - float & tc tab (typical)
- Figure 17 - Installation WEB Applet - lvd tab (typical)
- Figure 18 - Installation WEB Applet - digital i/p tab (typical)
- Figure 19 - Installation WEB Applet - rectifiers tab (typical)
- Figure 20 - Installation WEB Applet - shunts tab (typical)
- Figure 21 - Battery Management WEB Applet (typical)
- Figure 22 - Alarm Matrix WEB Applet (typical)
- Figure 23 - Alarm Matrix WEB Applet - matrix options (typical)
- Figure 24 - Alarm Matrix WEB Applet - temperature alarm settings (typical)
- Figure 25 - Alarm Matrix WEB Applet - voltage alarm settings (typical)
- Figure 26 - Alarm Matrix WEB Applet - voltage alarm settings (typical)
- Figure 27 - Alarm Matrix WEB Applet - other alarm settings (typical)
- Figure 28 - Network Settings WEB Applet (typical)
- Figure 29 - Alarm Log WEB Applet (typical)
- Figure 30 - Data Log WEB Applet (typical)
- Figure 31 - Change Password WEB Applet
- Figure 32 - Help WEB Page
- Figure 33 - About WEB Page (typical)
Page 59
X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
4. Controller - Identity, System, Compliance
Parameter Name Function
controllerPartNumber Controller part number.
controllerSerialNumber Controller serial number.
controllerRevision Controller revision level.
systemPartNumber System part number.
systemModelNumber System model number.
systemRevision System revision level.
systemSerialNumber System serial number.
controllerFreeRAM Amount of free RAM in the controller.
controllerFreeFlash Amount of free Flash Memory in the controller
controllerTotalRAM Total amount of RAM tted in the controller.
controllerTotalFlash Total amount of ash memory tted in the controller.
controllerState Status of the main program running in the Java Virtual Machine.
0=Stopped, 1=Starting, 2=Running, 3=Failed.
controllerReboot Writing a 1 to this register will reboot the controller.
mibCompliance Compliance statement for the UNIPOWER Controller 2 agent that
implements this enterprise MIB module.
mibGroup Objects in this enterprise MIB module for the UNIPOWER Controller 2.
5. Traps
Parameter Name Function
batteryOTATrapOn One of the battery temperatures has exceeded the battery over
temperature ON threshold. [1 only in X75]
batteryOTATrapOff One of the battery temperatures has fallen below the battery over
temperature OFF threshold. [1 only in X75]
batteryUTATrapOn One of the battery temperatures has fallen below the battery under
temperature ON threshold. [1 only in X75]
batteryUTATrapOff One of the battery temperatures has exceeded the battery under
temperature OFF threshold. [1 only in X75]
externalOTATrapOn The external temperature has exceeded the external over temperature
ON threshold.
externalOTATrapOff The external temperature has fallen below the external over
temperature OFF threshold.
externalUTATrapOn The external temperature has fallen below the external under
temperature ON threshold.