X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
Parameter Name Function
rectierOCA Rectier over current alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
loadOCA Load over current alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
batteryOCA Battery over current alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
batteryODA Battery on discharge alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
digitalAlarmx
(x = 1 to 16)
Digital input x alarm. [1 only in X75]
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
nRectAlarm Insufcient rectiers alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
acfAlarm AC Failure alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
rectThermalAlarm Rectier thermal alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
rectFanAlarm Rectier fan alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
singleRFA Single rectier failure alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
multiRFA Multiple rectier failure alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
eqAlarm Equalization active alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
bTestAlarm Battery test active alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
bProbexDisAlarm
(x = 1 or 2)
Battery temperature probe x disconnected alarm. [1 only in X75]
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
bProbexShortAlarm
(x = 1 or 2)
Battery temperature probe x shorted alarm. [1 only in X75]
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
extProbeDisAlarm External temperature probe disconnected alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
extProbeShortAlarm External temperature probe shorted alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
bTestFailAlarm Battery test failure alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
digitalInputx
(x = 1 to 16)
Digital input is Closed (0) or Open (1). [1 only in X75]