User's Manual

Table Of Contents
Page 54
X75 SERIES - Mk3 Controller
INSTALLATION & OPERATING MANUAL
Manual No. x75mk3-11
x75-man-Rev11-0815.indd
Appendix 1 – SNMPv3 MIB Information
The SNMP feature provides status read-out and alarm trapping only. All parameters described in
this appendix are therefore read-only.
Parameters for X75 Remote Access Controller MIB are organized into groups and are briey
described as follows. For complete details please view the MIB in a text viewed such as Windows
Notepad.
1. Logic Groups - Number of rectiers, Alarm State Table, Digital Input State Table, Relay Out-
put State Table, LED Output State Table, LVD Output State Table.
Parameter Name Function
numberOfRectiers The number of rectiers that are detected as being present.
kx
(x = 1 to 8)
Relay Kx is OFF (0) or ON (1). [1-4 only in X75]
majLED Major Alarm LED is OFF (0) or ON (1).
minLED Minor Alarm LED is OFF (0) or ON (1).
acfLED AC Fail LED is OFF (0) or ON (1).
rfaLED Rectier Failure LED is OFF (0) or ON (1).
otaLED Over temperature alarm LED is OFF (0) or ON (1).
lvdx
(x = 1 or 2)
Driver for LVDx is OFF (0) or ON (1). [1 only in X75]
buzzer Alarm sounder is OFF (0) or ON (1).
batteryOTA Battery over temperature alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
batteryUTA Battery under temperature alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
externalOTA External over temperature alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
externalUTA External under temperature alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
controllerOTA Controller over temperature alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
controllerUTA Controller under temperature alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
overVoltageAlarm Over voltage alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
lowVoltageAlarm Low voltage alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.
lowlowVoltageAlarm Low low voltage alarm.
(0) CLEAR, (1) OTHER, (2) MINOR, (3) MAJOR.