The Rectiers tab is used to set up the rectier type to use with the system. There
are currently three options:
RPCP/M/RSG (I²C based communications)
RRS/RPCG (I²C based communications)
RBSR (PMBus™ based communications)
EnableDCVoltagewalk-incheckbox. This allows the system to slowly raise the
system voltage (generated from the rectiers) in about 30 seconds up to the nominal
voltage. This can be useful to limit load on a generator or slowly increase the battery
charging current. Note that the rectiers will operate at their default voltage setting
for around 20 seconds before the controller has booted up when a system is rst
powered up.
X75 supports RSG type rectiers, so RPCP/M/RSG is set by default. This setting
should not be changed.
13.3.9 - Current
Figure20-InstallationWEBApplet-shuntstab(typical)
The Current tab allows a system to be congured to use zero, one or two shunts.
X75 uses a 2 shunt conguration and this is set by default. This setting should not
be changed.