CalculatedMaximumFloatVoltage. This is the maximum voltage that the system
can adjust to given the temperature compensation slope, nominal oat voltage and
temperature compensation temperature limits.
CalculatedMinimumFloatVoltage. This is the minimum voltage that the system
can adjust to given the temperature compensation slope, nominal oat voltage and
temperature compensation temperature limits.
EnableTemperatureCompensationcheckbox. If this box is checked, the system
will apply temperature compensation to the oat voltage. If not, the system will
always output the nominal oat voltage unless equalization, testing or charge current
limit is active.
13.3.3-Battery
Figure15-InstallationWEBApplet-batterytab(typical)
The Battery tab allows data about the batteries attached to the system to be entered
as below:
Numberofcells. This is used in the calculation of temperature compensation. It
is the total number of cells in one battery string (e.g. normally 24 cells for a 48V
system with 2V per cell lead acid cells)
Systemvoltage. Choose from 12, 24 or 48V.
NumberofStrings. Number of strings of batteries attached to the system. Note
that X75 only allows connection of a single battery string and that this setting should
therefore be 1 or 0 (if no batteries are connected).