User's Manual Part 1
Chapter 3 Installation
3.14 AC Power
3.14.1 General Requirements
A certified Electrician should connect the repeater to the building/site electrical service panel
to meet all local and national electrical codes, and according to the repeater electrical
drawing(s).
• AC Supply Voltage: 190 – 264 VAC (208 VAC nominal), Single Phase
• Frequency: 47 to 63 Hz
• Power Consumption: 6.1 kVA max.
Verify that the AC supply voltage is within the specified range and check
all power cables for damage.
3.14.2 Repeater Cabinet Ground Connection
The repeater cabinet must be connected to the building/site’s main
ground terminal.
An external ground conductor can be secured to the ground stud located on the left side of
the cabinet using the XX nut – see Figure 3-36
. A torque rating of XX In. Lbs. should be used
to tighten the nut.
SX03-10000-01-M01 3-44