X75 SERIES
INSTALLATION & OPERATING MANUAL
Manual No. x75-10b
x75-man-Rev10b-0514.indd
6.0 GENERAL SPECIFICATIONS
6.1 Inputs
Supply Voltage: 85-264VAC Single Phase
Each rectier position is supplied via an individual
IEC60320 C14 Inlet Socket.
A 3-phase supply may be connected provided that the voltage presented to each
individual rectier position does not exceed 264VAC.
Supply Current: Max 9A input @ 85-264VAC per inlet socket.
Battery Input: Direct connection to DC output bus or via protection
breakers.
Digital alarm inputs: Volts free contact input*
*Volts free contacts are internally pulled up to 5V with reference to rectier negative
sense, these lines should not be tied to anything other than volts free contacts or
oating opto-coupler outputs.
Temperature probes: Sensor with output current proportional to temperature.
6.2 Outputs
Pluggable Breakers: Up to 5 circuits, 30A max. per circuit.
GMT Fuses: 10 circuits, 12A max. per circuit.
Alarm Relay Contacts: Form C, 1A max at 30VDC.
Ethernet: 10/100 Base T.
6.3 Protection
Supply Input: Each rectier is individual fused internally.
Battery: 100A Magnetic Circuit Breaker.
Output Distribution: According to installed circuit breakers or fuses.
Bulk DC Bus: Rectier Current Limiting / Battery Breaker.