User's Manual
Table Of Contents
- 1.0 INTRODUCTION
- 2.0 FEATURES & OPTIONS
- 3.0 SAFETY WARNINGS
- 4.0 WARRANTY (summary)
- 5.0 UNPACKING AND INSPECTION
- 6.0 GENERAL SPECIFICATIONS
- 7.0 PRINCIPAL OF OPERATION
- 8.0 FRONT PANEL DESCRIPTION
- 9.0 REAR PANEL DESCRIPTION
- 10.0 LED Indicators
- 11.0 MAKING CONNECTIONS TO THE X75
- 12.0 INSTALLATION
- 13.0 USING THE CONTROLLER WEB BROWSER INTERFACE
- Appendix 1 – SNMP MIB Information
- Appendix 2 – Load LVD Configuration (model X75-12-A-GHHIL-S-578 only)
- Appendix 3 – Revision History
- Figure 1 - X75 Compact Integrated DC Power System
- Figure 2 - Block Schematic
- Figure 3a - Front View with Breakers (configuration A)
- Figure 3b - Front View with GMT Fuses (configuration B)
- Figure 4 - Rear Views of Base and Expansion Units
- Figure 5 - LED Indicators
- Figure 6 - Recommended Load Circuit Wire Sizes
- Figure 7 - Battery Temp. Probe & Alarm Relay Connector Pin-Out
- Figure 8 - Ethernet Connector Pin-Out
- Figure 9 - Auxiliary Connector Pin-Out
- Figure 10 - Input Current Ratings
- Figure 11 - Controller Status WEB Page (typical)
- Figure 12 - Rectifier Status WEB Page (typical)
- Figure 13 - Rectifier I²C Addressing
- Figure 14 - Controller Factory Calibration WEB Page (typical)
- Figure 15 - Controller Site Installation WEB Page (typical)
- Figure 16 - Alarm Configuration WEB Page (typical)
- Figure 17 - Controller Network Settings (typical)
- Figure 18 - Controller Alarm Log WEB Page (typical)
- Figure 19 - Controller Control Panel WEB Page (typical)
- Figure 20 - Controller System Settings WEB Page (typical)
- Figure 21 - SNMP Configuration WEB Page (typical)
- Figure 22 - Controller Help WEB Page (typical)
- Figure 23 - About UNIPOWER Telecom WEB Page (typical)
Page 34
X75 SERIES
INSTALLATION & OPERATING MANUAL
Manual No. x75-10b
x75-man-Rev10b-0514.indd
TEMPERATURE COMPENSATION
Temp Comp (mV/°C/Cell) – Enter the temperature compensation slope value in
accordance with the specications of the batteries that are being employed with the
system.
Number Of Cells – Enter the total number of battery cells.
Max Temp (°C) – Enter the maximum temperature at which temperature
compensation may be applied. Above this temperature the X75 will cease to apply
further compensation to the oat voltage.
Min Temp (°C) – Enter the minimum temperature at which temperature compensation
may be applied. Below this temperature the X75 will cease to apply further
compensation to the oat voltage.
VOLTAGE ALARMS
OVA – Enter the voltage above which the Over-Voltage Alarm will be triggered.
UVA – Enter the voltage below which the Under-Voltage Alarm will be triggered.
EVA – Enter the voltage below which the End-Voltage Alarm will be triggered.
TEMPERATURE ALARMS
Battery OT – Enter the temperature at which the battery Over-Temperature alarm
will be triggered.
External OT/UT – Enter the temperature at which the external Over-Temperature
and Under-Temperature alarms will be triggered.
Controller OT – Enter the temperature at which the controller’s internal Over-
Temperature alarm will be triggered. THIS SETTING SHOULD NOT NORMALLY
BE CHANGED.