User's Manual

Table Of Contents
Page 28
X75 SERIES
INSTALLATION & OPERATING MANUAL
Manual No. x75-10b
x75-man-Rev10b-0514.indd
This page presents two blocks of information. The top block displays a number
of system status parameters by mimicking a block of LEDs. 7 of these functions,
described earlier, are displayed on the front panel of the system unit.
The bottom block of information shows the following ‘live’ data:
Bus Voltage
Battery Current
Rectier Current
Load Current
Battery Temperature
External Temperature
Controller Temperature
No. of Rectiers Installed (includes all rectiers that are present regardless
of status)
If the battery or external temperature probes are not connected a reading of 25ºC
will be displayed by default.