User's Manual
Table Of Contents
- 1.0 INTRODUCTION
- 2.0 FEATURES & OPTIONS
- 3.0 SAFETY WARNINGS
- 4.0 WARRANTY (summary)
- 5.0 UNPACKING AND INSPECTION
- 6.0 GENERAL SPECIFICATIONS
- 7.0 PRINCIPAL OF OPERATION
- 8.0 FRONT PANEL DESCRIPTION
- 9.0 REAR PANEL DESCRIPTION
- 10.0 LED Indicators
- 11.0 MAKING CONNECTIONS TO THE X75
- 12.0 INSTALLATION
- 13.0 USING THE CONTROLLER WEB BROWSER INTERFACE
- Appendix 1 – SNMP MIB Information
- Appendix 2 – Load LVD Configuration (model X75-12-A-GHHIL-S-578 only)
- Appendix 3 – Revision History
- Figure 1 - X75 Compact Integrated DC Power System
- Figure 2 - Block Schematic
- Figure 3a - Front View with Breakers (configuration A)
- Figure 3b - Front View with GMT Fuses (configuration B)
- Figure 4 - Rear Views of Base and Expansion Units
- Figure 5 - LED Indicators
- Figure 6 - Recommended Load Circuit Wire Sizes
- Figure 7 - Battery Temp. Probe & Alarm Relay Connector Pin-Out
- Figure 8 - Ethernet Connector Pin-Out
- Figure 9 - Auxiliary Connector Pin-Out
- Figure 10 - Input Current Ratings
- Figure 11 - Controller Status WEB Page (typical)
- Figure 12 - Rectifier Status WEB Page (typical)
- Figure 13 - Rectifier I²C Addressing
- Figure 14 - Controller Factory Calibration WEB Page (typical)
- Figure 15 - Controller Site Installation WEB Page (typical)
- Figure 16 - Alarm Configuration WEB Page (typical)
- Figure 17 - Controller Network Settings (typical)
- Figure 18 - Controller Alarm Log WEB Page (typical)
- Figure 19 - Controller Control Panel WEB Page (typical)
- Figure 20 - Controller System Settings WEB Page (typical)
- Figure 21 - SNMP Configuration WEB Page (typical)
- Figure 22 - Controller Help WEB Page (typical)
- Figure 23 - About UNIPOWER Telecom WEB Page (typical)
Page 14
X75 SERIES
INSTALLATION & OPERATING MANUAL
Manual No. x75-10b
x75-man-Rev10b-0514.indd
Expansion shelves are supplied with a short cable to link the J1 connectors between
the base unit and the expansion shelf.
9.7 Above J1 is a 4-way Spring Clamp Terminal connector. This connector, designated
J2, provides terminations for the auxiliary digital alarm input and the optional external
temperature probe. The pin-out for this connector is described in section 11.
9.8 To the left of J2 is the Ethernet TCP/IP connector (J3). This connection uses a standard
RJ45 Network connector. It is used to connect either to a Local Area Network or
directly to a PC with network connection, the latter using a standard cross-over cable.
The primary means of setting up the X75 unit is via it’s built-in WEB server, which
is accessed using a WEB browser via this Ethernet TCP/IP connection.
9.9
At the right hand side of the base unit and also the expansion shelf are three IEC60320
C14 inlets. These provide individual AC input feeds to each of the 3 rectier slots.
The X75 employs UNIPOWER Sigma Series rectiers which operate from a
Universal 85-264VAC 50-60Hz single phase supply. The system is designed so that
various single and 3-phase supply connections can be made. For example, in the
U.S. it might be desirable to connect each rectier between two 120VAC phases; in
which case each rectier is operating at 208VAC.
IMPORTANT NOTE: DO NOT CONNECT THE UNIT SUCH THAT MORE
THAN 264VAC WILL BE PRESENT BETWEEN THE LIVE AND NEUTRAL
TERMINALS OF ANY ONE INLET SOCKET. SUCH CONNECTION MAY
BE HAZARDOUS, WILL DAMAGE THE UNIT AND INVALIDATE THE
WARRANTY.