Specifications
INVO SERIES INVERTER/CHARGER
INSTALLATION & OPERATING MANUAL
Manual No. INVO-1 Page 15 08/11 invo-man
Table 6 - Inverter Mode Specifications
MODEL INVC5048H INVC5096H
Output Voltage Waveform Pure Sine Wave
Rated Output Power 5,000VA
Power Factor 0.84
Nominal Output Voltage 230Vac
Output Frequency 50Hz / 60Hz ± 1Hz
Output Voltage Regulation ±10% rms
Nominal Efficiency >90%
Over-Load Protection
fault after 5s@≥150% load
fault after 10s@110%~150% load
Surge rating 10,000VA
Capable of starting electric motor 2.5HP
Output Short Circuit Protection Current limit (Fault after 4 cycles max.)
Bypass Breaker Size 40A
Nominal DC Input Voltage 48V 96V
Min DC start voltage 40V 80V
Low DC Alarm 42.0 ± 1.2Vdc 84.0 ± 2.4Vdc
Low DC Alarm Recovery 43.2 ± 1.2Vdc 86.4 ± 2.4Vdc
Low DC Shut-down 40.0 ± 1.2Vdc 80.0 ± 2.4Vdc
Low DC Shut-down Recovery 44.0 ± 1.2Vdc 88.0 ± 2.4Vdc
High DC Shut-down 60.0 ± 1.2Vdc 120.0 ± 2.4Vdc
High DC Shut-down Recovery
1
58.0 ± 1.2Vdc 116.0 ± 2.4Vdc
Power saver setting
0W (Set “OFF” at LCD)
10W ±5W enter 5+/-2W leave (Set “ON” at LCD)
Tare loss(nominal)
Saver OFF:<50W
Saver ON:<10W
DC component of AC output <100mV
Half wave load detection Yes(when unbalance current>35A)
Power Limitation
Note 1: Line voltage must be available for charging.