Specifications

INVO SERIES INVERTER/CHARGER
INSTALLATION & OPERATING MANUAL
Manual No. INVO-1 Page 11 08/11 invo-man
OPERATION
Front Panel Controls and LCD Indicators
Figure 5 shows the controls and indicator lights on the front of the INVO Series inverter/charger. They
control and provide information in both inverter and battery charging modes of operation.
Figure 5 - Front Panel
Power ON/OFF
Located on the left of the panel is the ON/OFF Switch. Once the inverter/charger has been properly
installed and the batteries connected, press this switch to the ON position to switch on the
inverter/charger.
Important Note: INVO Series has a fail-safe system that will not allow it to switch on unless batteries
are connected and the charge voltage of the batteries is above 42V for the INV5048H and 82V for the
INV5096H.
Configuration Switch
On the right of panel are the 4 configuration switches which setup the inverter/charger operation
parameters. See table 3 for details.
Switch Function Description
up Move up to pre-select
down Move down to pre-select
configuration Enter configuration mode, and turn page
enter Enter to confirm
Table 3 - configuration button function
After you press configuration button and enter configuration mode, there is a total of 4 configuration
pages. Change the page by pressing the configuration button again.
Page Description Selectable option
1 Input range Normal / Generator / Wide Range
2 Output range 220V / 230V / 240V
3 Battery type AGM / GEL / FLOODED
4 Charger current 35A/20A(INVC5048H), 20A/10A(INVC5096H)
5 Saver mode ON/OFF
Note: The 220v and 240v output function is reversed for further feature.
Table 4 - configuration button function
On/Off
switch
LCD indicator
Configuration switches