PRICE: $25.00 INV2500-HS and INV5000-HS TELECOM INVERTERS OPERATING MANUAL www.unipowertelecom.com Manual No. INV-802-3 09/4/02 INV2500HS-5000HS-Man-Rev3 © 2002 UNIPOWER Corp. All Rights Reserved UNIPOWER Telecom, Division of UNIPOWER Corporation NORTH AMERICA • 3900 Coral Ridge Drive, Coral Springs, Florida 33065, USA • Tel: +1 954-346-2442 • Fax: +1 954-340-7901 • sales@unipower-corp.
CONTENTS SECTION TOPIC PAGE 1.0 Introduction 1 2.0 Important Features 1 3.0 Product Line 3 4.0 Safety Warnings 3 5.0 Warranty 4 6.0 Unpacking and Inspection 4 7.0 Description of Operation 5 8.0 Front and Back Panel Descriptions 5 9.0 Electrical Specifications 7 10.0 Mechanical Dimensions of Shelves 8 11.0 Safety and Industry Standards 8 12.0 Operating Information 10 13.0 Parallel Operation 13 14.0 Installation and Testing 15 15.0 Inverter Application 17 16.
ILLUSTRATIONS FIGURE TITLE PAGE 1 INV2500-HS and INV5000-HS Inverter Models 2 2 Front & Back of INV2500-HS Module 6 3 Front & Back of INV5000-HS System 6 4 Mechanical Dimensions of INV5000-HS & INVR2U-HS Shelves 9 5 INV2500-HS Inverter Output Waveforms 11 6 INV2500-HS & INV5000-HS Overload Characteristic 12 7 Connections for ORing Form C Relay Outputs on INV5000-HS 12 8 Inverter Module Pin Connections 14 9 Two 115VAC INVR2U-HSs in Parallel Using AC Distribution Panel 16 10 Out
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL INV2500-HS AND INV5000-HS TELECOM INVERTERS OPERATING MANUAL 1.0 2.0 INTRODUCTION 1.1 This Operating Manual should be read through carefully before installing and operating the INV2500-HS inverter modules or INV5000-HS inverter systems. See Figure 1. 1.2 The INV2500-HS is a 2500 volt-ampere hot-swap, telecom inverter module. It converts a nominal 48VDC input into a 115VAC output at 50 or 60Hz.
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL (a). INV2500-HS Inverter Module (b). INV5000-HS Inverter System Figure 1.
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL u u u u u u u u u u u u u u u u u 3.
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL 5.0 4.3 When operating these inverters, the chassis ground terminal must be connected to safety ground to minimize electrical shock hazard and to ensure low EMI (electromagnetic interference). 4.4 The internal voltages are at hazardous potentials. The inverter covers should not be removed. There are no user-serviceable components in these units. Removing the covers of the inverters will void the warranty.
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL 6.4 7.0 8.0 Always save the packing materials for later use in shipping the unit. Never ship the inverter without proper packing. DESCRIPTION OF OPERATION 7.1 The INV2500-HS modules employ MOSFET and IGBT power semiconductor switches with advanced, high-frequency, pulse modulation techniques to produce a low-distortion, 50 or 60Hz sine wave output with 90% efficiency and 7VA per cubic inch power density.
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL ä INV2500-HS FRONT VIEW 3.32 (84.3) ä 8.50 (216) ä ä INV2500-HS BACK VIEW HOT-SWAP CONNECTOR ä Figure 2. Front and Back of INV2500-HS Module INV5000-HS FRONT VIEW B SIDE ä A SIDE 3.46 (87.9) AC OUTPUT BREAKER DC INPUT BREAKER ä ä ä ä ä DC INPUT BREAKER AC OUTPUT BREAKER 18.32 (465) ä INV5000-HS BACK VIEW Figure 3.
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL or side B) of this inverter is a INV2500-HS. The back panel has a transparent plastic safety cover. The INVR2U-HS shelf with two INV2500-HS inverters in it is identical in appearance and dimensions to the INV5000-HS, both front and back. Both units have a front retention panel over the INV2500-HS modules. 8.4 9.0 On the INV5000-HS back panel to the left are the AC output screw terminals. At the center is a terminal strip with the Form C relay contacts N.O.
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL ENVIRONMENTAL Operating Temp. Range ...................................... * ............................... 0°C to 70°C ............................... * Output Current Derating ...................................... * ...................... 2.5%/°C, 50°C to 70°C ...................... * Storage Temp. Range ......................................... * ............................ -40°C to +85°C ............................ * Humidity .........................
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL ä 17.38 (441) 3.46 (87.9) ä 18.32 (465) ä ä Figure 4.
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL 12.0 OPERATING INFORMATION 12.1 Input Voltage. These telecom inverters operate off a nominal 48VDC input source which may be a battery or other DC source. The input voltage range is 42 to 56VDC. Input connections on the back of the INV5000-HS and INVR2U-HS are to bus bars with no. 1/4-20 studs. 12.2 Output Voltage.
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL 1 2 (a) Full Load Step. Vo (top) & Io (bot@20A/cm). 1 2 (b)Sudden Overload Applied. Vo (top) & Io (bot @ 50A/cm). 1 2 (c) Short Circuit Applied. Vo (top) & Io (bot @50A/cm). Figure 5.
Shutdown Time, Sec. INV2500-HS & INV5000-HS SERIES OPERATING MANUAL 0 0 10 20 20 40 30 60 40 80 50 100 60 120 70 140 80 160 INV2500-HS or 230VAC INV5000-HS 2- INV2500-HS IN INVR2U-HS Output RMS Amperes Figure 6. INV2500-HS & INV5000-HS Overload Characteristic. (a) Normally Open (b) Normally Closed Figure 7.
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL shutdown times shown in the table, the output will be shut down and must be reset by turning both input and output circuit breakers off. After this, the input breaker(s) should be turned back on (up position); after the Output OK LED(s) come on the output breaker(s) should be turned back on (up position). 13.0 12.5 Grounding. The DC input ground, AC output ground, AC neutral and chassis ground are all in common.
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL J1 J1 Connector: Positronics GFSH01M182 3 2 1 6 5 4 9 8 7 11 10 12 15 14 17 16 19 18 21 20 13 24 27 30 33 23 Mating Connector: Positronics GFSH01F10 Contacts No. FC112N2 for Pins 1, 3, 5, 7, 8, 25-28 and 30-33. Conacts No. FC720N2 for Pins 14-18.
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL more inverters. Current sharing between paralleled inverters is ±10%. 13.2 Alternatively, separate sources may be used for the inputs to these inverters while the outputs are connected in parallel. In either case, output loads should have individual distribution circuit breakers. The following table shows output current and total volt-amperes for inverters connected in parallel.
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL AC OUTPUTS Figure 9. Two 115VAC INVR2U-HSs in Parallel Using AC Distribution Panel INVR2U-HS INV5000-HS-230 Figure 10.
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL by means of the 1/4-20 studs. Connect the input ground (10-32 stud) to the system ground. Make sure the correct polarity is used and make sure the connections are clean and firm. Reversed input polarity could cause damage to the inverter. 15.0 14.4 Connect the AC output cable to the proper output screw terminals. See Figure 10 for the correct connection for 115 or 230VAC output versions.
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL 16.0 15.3 Take one of the inverter modules and turn the DC input circuit breaker on; then after the Output OK LED has come on turn the AC output circuit breaker on. This sequence must be performed for the inverter A side and then the B side. Repeat this for each paralleled inverter in turn until all inverters are on. Make sure that the three green LEDs are on for each inverter. 15.
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL 17.0 16.5.3 Replace the front rention panel by replacing the four Phillips screws. 16.5.4 Turn on the DC input breaker (up position). 16.5.5 After the Output OK LED comes on, turn on the AC output breaker (up position). 16.5.6 All green LEDs on the inverter modules should now be on, indicating normal operation.