System information

GRAVITAS SABRE SERIES
INSTALLATION &OPERATING MANUAL
Manual No. SABRE-4 Page 39 11/27/07 sabre-man
Figure 23 Communications interfaces on the rear of the controller
3.7.2 Dry contact Alarm Settings
A. SettingsÆSystemÆDry contact Press ‘Enter’ entry the follow menu
D r y C o n t : 1
A l a r m T y p e : I N V
A l a r m N O : 0 2
I n v o v e r l o a d
B. Press ‘Up’ or ‘Down’ to select the dry contact, then enter the menu to set the alarm mode of the dry contact.
I n v
S T S
C o n t
S m r
A l a r m T y p e : I n v
A l a r m N o : 0 1
I n v f a u l t
Press ‘Up’ or ‘Down’ to select alarm mode of the dry contact relay outputs.
The default alarm mode is programmed as follows:
No. Inverter No. Static Transfer Switch
01 Inverter fault 01 STS failure
02 Inverter over load 02 STS K2 off
03 Inverter fan fault 03 STS SCR1 short circuit
04 Inverter power limit 04 STS SCR2 short circuit
05 Inverter input fault 05 STS bypass can not user
06 Inverter low volt off 06 STS backfeed
07 STS fan failure
08 STS EEPROM failure
09 STS not respond
No. Controller No. SMR
01 Bat voltage low 01 Over Voltage
02 Controller temperature high 02 Over temperature