MBS Status Schematic operation principle of STS Description
Normal
Operation (P3)
Mains
Inverter
Load
Backfeed Relay
Bypass Relay
MBS Main Contact1
MBS Main Contact2
SCR1
SCR2
Normal Operation(NORM)
Mains priority:
Mains AC powers the
load through the static
switch
MBS can be switched
from P3 to P2 and P4
position
SCR2 open, SCR1 and
Back-feed Relay closed
When the mains voltage
or frequency is abnormal,
and the inverter is normal,
the STS transfers to
on-line mode
When SCR2 is short, the
STS will keep the off-line
mode
Normal
Operation (P3)
Mains
Inverter
Load
Backfeed Relay
Bypass Relay
MBS Main Contact1
MBS Main Contact2
SCR1
SCR2
Normal Operation(NORM)
Inverter priority:
Inverters power the load
through the STS
MBS can be switched
from P3 to P2 and P4
position
SCR1 open, SCR2 and
Back-feed Relay closed
When the Inverter’s
voltage or frequency is
abnormal, and the mains
is normal, the STS
transfers to off-line mode
When SCR1 is short, the
STS will keep the
on-line mode, and the
Back-feed relay will
open