Installation manual

UNIPOWER
Installation manual PQ Secure
24
4.4.6 HV 3-phase measurement with 3CT’s and 3PT’s (Line-to-line voltages)
Figure 14
The above wiring diagram is used for three-phase measurement in electricity networks with 3 CT´s
and 3 PT’s. The voltage channels of the unit are connected to PT’s (normally 110 V AC secondary),
for supplying line-to-line voltages, and current channels are connected to CT´s (normally 1 - 5 A AC
secondary). Always protect the voltage inputs with a 1A fuse in each conductor (red conductor) on
the secondary side of the PT. The connection for this type of measurement is as follows:
Channel: Measured object: Channel: Measured object:
U1+ = L1 PT+ I1+ = L1 CT+
U1- = L2 PT+ I1- = L1 CT- (Grounded)
U2+ = L2 PT+ I2+ = L2 CT+
U2- = L3 PT+ I2- = L2 CT- (Grounded)
U3+ = L3 PT+ I3+ = L3 CT+
U3- = L1 PT+ I3- = L3 CT- (Grounded)
Note: This configuration is normally used in medium voltage networks.
1A