Installation manual

UNIPOWER
Installation manual PQ Secure
20
4.4.2 3-phase measurement with direct voltage, 3 CT´s and neutral (Line-to-neutral voltages)
Figure 10
The above wiring diagram is used for three-phase measurement in low voltage networks. The voltage
channels of the unit are connected directly to the electricity network for measuring line-to-neutral
voltages (230 V) and therefore do not require any instrument transformers (PT). However, the
current channels are connected to existing instrument transformers, allowing the measurement of
high currents, e.g. directly from the secondary side of a power transformer. Always protect the
voltage inputs with a 1A fuse in each conductor (red conductor). The connection for this type of
measurement is as follows:
Channel: Measured object: Channel: Measured object:
U1+ = L1 I1+ = L1 CT+
U1- = (Neutral) I1- = L1 CT- (Grounded)
U2+ = L2 I2+ = L2 CT+
U2- = (Neutral) I2- = L2 CT- (Grounded)
U3+ = L3 I3+ = L3 CT+
U3- = (Neutral) I3- = L3 CT- (Grounded)
Note: In power quality standards such as EN 50160 and the Swedish SS 421 18 11 (low voltage
quality standard) measurements in low voltage networks are always based on line-to-
neutral voltages, i.e. U
num
= 230V. This means that it is important to connect the unit for
line-to-neutral voltages and not for line-to-line voltages.
1A
1A
1A