Data Sheet
23
4.5 Relay outputs
4.6 Installation and operating conditions
Maximum output voltage
10 V
Maximum output current
20 mA
Output voltage accuracy
±0.5%
Output current accuracy
±0.5%
Resistance measurement
accuracy 0 – 2kOhm
±0.5%
Pt1000 measurement accuracy
±0.5%
Output screw connectors
RO
Common ground
COM
Galvanic isolation
Yes
Type of output
Electromechanical unprotected relay
Switched voltage
250 V AC/30 V DC
Switched current
5A
Short-term
5A
COM current
10A
Time to switch on/off
10ms
Mechanical lifetime
5 000 000
Electrical lifetime
100 000
Short circuit protection
No
ESD protection
No
Inductive load solution
External – RC, varistor, dioda
Isolation voltage
4 000 V AC
Operating temperature
0 °C .. + 55 °C
Storage temperature
-25 °C .. +70 °C
Dielectrical strength
In accordance with EN 60950
Degree of protection IP (IEC 529)
IP20
Operation position
Vertical
Installation
On DIN rail 35 mm into distribution boxes
Wire connection
Removable screw connectors
Wire gauge
Max. 2,5 mm
2
Connector screw torque
Max. 0,4 Nm