Operations Manual

dicated in Table 18 , the fire suppression system has failed the
maintenance test. Refer to the Troubleshooting Manual.
IMPORTANT: If the fire suppression system failed
the maintenance test, DO NOT operate the tumble
dryer.
Dry
Weight
Wet
Weight
Mini-
mum
Weight
lbs.
[kg]
lbs.
[kg]
lbs.
[kg]
50 25 [11] 40-44
[18-20]
35 [16]
75 40 [18] 57-61
[26-28]
52 [24]
Table 18
9. Clean up any water on the floor.
10. Lock the fire suppression system control box.
11. If the separate alarm option is being used, reconnect the auxil-
iary alarm output.
12. Start the tumble dryer to dry the test load.
13. On maintenance record, check box if fire suppression system
passed the test, date and sign record.
TMB2010N_SVG
2
1
1. Spray Manifold
2. Water Spray
Figure 71
Maintenance
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
96 Part No: 70457901ENR14