Operations Manual

One Manifold Assembly
TMB2403N_SVG
L
K
J
I
H
G
F
E
D
C
B
A
1
2
1. Outlet duct diameter = largest duct diameter based on number of tumble dryers
2. 45° typical
Figure 20
Duct Station 050/075 F75
A 8 in. [203 mm] 10 in. [254 mm]
B 12 in. [305 mm] 15 in. [381 mm]
C 15 in. [381 mm] 18 in. [457 mm]
D 17 in. [432 mm] 21 in. [533 mm]
E 19 in. [483 mm] 24 in. [610 mm]
F 21 in. [533 mm] 26 in. [660 mm]
G 23 in. [584 mm] 28 in. [711 mm]
H 25 in. [635 mm] 30 in. [762 mm]
I 26 in. [660 mm] 32 in. [813 mm]
J 27 in. [686 mm] 33 in. [838 mm]
K 29 in. [737 mm] 35 in. [889 mm]
L 30 in. [762 mm] 36 in. [914 mm]
Table 4
NOTE: Table 4 represents tumble dryers with the same
vent size. If multiple vent sizes are used, consult a lo-
cal HVAC specialist.
NOTE: Duct clean-out recommended every 6 feet [0.18
m].
Exhaust Requirements
©