LINE VOLTAGE ELECTRICAL SYSTEM
DIESEL GENERATOR
An Onan model SD 20.0HDKAW-2008A, diesel driven generator shall be installed on the vehicle. The generator shall be
installed so that fumes, vapors, heat, and vibrations do not enter the driving or crew compartment. The generator shall be
rated at 20,000 watts continuous at 120/240 VAC, 166/83 amps, single phase. Current frequency shall be stable at 60
hertz.
Generator features shall include:
•
4-cylinder Kubota V2403-M diesel engine
•
Digital voltage regulation
•
Brushless alternator
•
Regulated-voltage 30 A battery charging
•
Vibration isolated control box
•
Hourmeter
•
Muffler USDA approved spark arrestor
•
Instant one touch stop
•
Internal radiator
•
Electric fuel pump
•
Bottom mount radiator
•
Vertically mounted fuel filter, spin on cartridge
•
Intake silencer
•
Full flow oil filter
•
Replaceable element air cleaner
•
Automatic timed glow plugs for quick easy start
• Maintenance-free electronic governor
• Overvoltage, low oil pressure, overtemp,
overspeed, overload, and AC alternator overtemp
safeties
Overall size of generator shall 49" L x 24" W x 28" H and weigh 890 lbs.
Sound: 60 Hz (single phase) 81.9 dB(A) at 10 ft before installation, full load.
Generator shall be equipped with a high temperature automatic shutdown system and a low oil (pressure or level)
automatic shutdown system. The generator shall be installed in accordance with the generator manufacturer’s
requirements for ventilation and service accessibility.
If the generator is installed in a compartment and the compartment doors must be open during its operation, the generator
shall be equipped with an interlock system to prevent its operation if the doors are not open, or the compartment shall be
equipped with a high temperature alarm.
Permanently installed generators shall have readily accessible engine oil drain provisions or piping to a remote location
for oil changing.
If the generator is located in a position on the apparatus where the operator cannot see the instrumentation and operate
the controls while standing at ground level or positioned at a specifically designated operator station, an operating panel
with the required instrumentation, start and stop controls, and other controls necessary for safe operation shall be
provided at a remote operator’s panel.
WARRANTY PERIOD
Provided such goods are operated and maintained in accordance with Onan's written instructions, Onan warrants that the
Generators shall be free from defects in material and workmanship for a period of two (2) years or two thousand (2,000)
hours, whichever comes first, from the date of delivery to the first purchaser.