LINE VOLTAGE ELECTRICAL SYSTEM
DIESEL GENERATOR
An Onan model SD 20.0HDKAW-2008A, diesel driven generator shall be installed on the vehicle. The generator shall be
installed so that fumes, vapors, heat, and vibrations do not enter the driving or crew compartment. The generator shall be
rated at 20,000 watts continuous at 120/240 VAC, 166/83 amps, single phase. Current frequency shall be stable at 60
hertz.
Generator features shall include:
4-cylinder Kubota V2403-M diesel engine
Digital voltage regulation
Brushless alternator
Regulated-voltage 30 A battery charging
Vibration isolated control box
Hourmeter
Muffler USDA approved spark arrestor
Instant one touch stop
Internal radiator
Electric fuel pump
Bottom mount radiator
Vertically mounted fuel filter, spin on cartridge
Intake silencer
Full flow oil filter
Replaceable element air cleaner
Automatic timed glow plugs for quick easy start
Maintenance-free electronic governor
Overvoltage, low oil pressure, overtemp,
overspeed, overload, and AC alternator overtemp
safeties
Overall size of generator shall 49" L x 24" W x 28" H and weigh 890 lbs.
Sound: 60 Hz (single phase) 81.9 dB(A) at 10 ft before installation, full load.
Generator shall be equipped with a high temperature automatic shutdown system and a low oil (pressure or level)
automatic shutdown system. The generator shall be installed in accordance with the generator manufacturer’s
requirements for ventilation and service accessibility.
If the generator is installed in a compartment and the compartment doors must be open during its operation, the generator
shall be equipped with an interlock system to prevent its operation if the doors are not open, or the compartment shall be
equipped with a high temperature alarm.
Permanently installed generators shall have readily accessible engine oil drain provisions or piping to a remote location
for oil changing.
If the generator is located in a position on the apparatus where the operator cannot see the instrumentation and operate
the controls while standing at ground level or positioned at a specifically designated operator station, an operating panel
with the required instrumentation, start and stop controls, and other controls necessary for safe operation shall be
provided at a remote operator’s panel.
WARRANTY PERIOD
Provided such goods are operated and maintained in accordance with Onan's written instructions, Onan warrants that the
Generators shall be free from defects in material and workmanship for a period of two (2) years or two thousand (2,000)
hours, whichever comes first, from the date of delivery to the first purchaser.