Instruction manual
8
i
.LON 100
e3
Hardware Guide
auto-ranging, auto-setting mains power supply. It is not necessary to adjust any
jumpers or other settings when connecting the
i
.LON 100 server to power mains.
The high voltage connection is implemented on screw terminals 1 (earth ground),
3 (Neutral), and 4 (Line). Screw terminal 2 (NC) is not used, and should remain
unconnected. A solid earth ground via terminal 1 connection is required for
proper ESD and EMC performance of the
i
.LON 100 device. Use this order when
connecting the screw terminals:
1. Insert the earth ground connection.
2. Insert the neutral connection.
3. Insert the line connection.
DO NOT apply power to the
i
.LON 100 server until you have checked all wiring
connections and you are instructed to apply power. Figure 1.4 shows the power
mains screw terminals.
Figure 1.4
i
.LON 100 Server High Voltage Mains Screw Terminals
Table 1.1 lists the enclosure marking for each of the power mains screw
terminals.
Table 1.1
i
.LON 100 Server AC Power Mains Connections
Screw Terminal Enclosure Marking Mains Connection
1 E Earth ground
2 NC Do not connect
3 N Neutral
4 L Line