Instruction manual

46
Inspections and maintenance
Inspections and maintenance performed pro-
fessionally and according to a regular sche-
dule as well as the use of original spare par-
ts are of the utmost importance for fault-free
operation of the boiler and to guarantee its
long life.
Yearly maintenance of the appliance is man-
datory in compliance with Laws in force.
Failure to perform Inspections and Mainte-
nance can entail material and personal da-
mage.
We therefore recommend stipulating an inspection or mainte-
nance contract.
Inspections help to determine the actual status of the applian-
ce and to compare it with the nominal status. This is done
through measuring, controls and observation.
Maintenance is required to eliminate any differences betwe-
en the actual status and the nominal status. This is normally
done by cleaning, setting and replacing individual compo-
nents subject to wear.
Maintenance intervals and their extent are determined by a
specialist based on the status of the appliance ascertained
through inspection.
Inspection and maintenance instructions
To assure long-term functioning of your ap-
pliance and to avoid altering its approved sta-
tus, only original Unical spare parts must be
used.
Before proceeding with maintenance, always perform the fol-
lowing operations:
Disconnect the electric mains switch.
Isolate the appliance from the electric mains by means of
an isolated device with a contact opening of at least 3 mm
(e.g. safety devices or power switches) and make sure
that it cannot be re-connected accidentally.
Close the gas shut-off valve upstream the boiler.
Close any shut-off valves on the heating flow and return
pipes.
After having completed all maintenance work, always per-
form the following operations:
Open the heating flow and return pipes.
If necessary, restore the heating system pressure until it
reaches the static pressure relative to the highest point of
the system.
Open the gas shut-off valve.
Reconnect the appliance to the electric mains and enga-
ge the switch.
Make sure the appliance is gas tight and watertight.
Vent the heating system and restore pressure if neces-
sary.
Should you decide to temporarily deactivate the boiler, you
must:
a) shut off the various supplies: electric, water and fuel;
b) empty the water system if antifreeze is not used.
4
INSPECTIONS AND
MAINTENANCE