Manual

Key Installation Practice #4
Waterproof all communication cable splices using DBY-6 and DBR-6 by 3M
®
. If using other waterproofing method,
verify that it is rated at 40 VDC minimum.
Key Installation Practice #5
Two Wire Decoder Systems must be properly grounded in order to protect against lightning surges. The communication
cable must be grounded no further than 1000 (305m) from any decoder. In high lightning areas, Toro recommends
that a decoder be no more than 500 (152m) from a surge device/ground plate, or total of 1000 (305m) between
ground plates. The surge device must be a Toro DEC-SG-LINE and must be grounded to a copper plate that is at least
4’’ x 36’’ x 0.064’’ (10.16cm x 91.4cm x 1.6mm). The minimum distance between the surge arrestor and the ground plate
should be 3 (91.4cm). Toro recommends a split bolt connection to be used to connect the surge device to the ground
wire with a DBM waterproof connector.
Note: A best practice on installation
to avoid surge/lightning damage is to
locate the decoder as close to the
valve(s) as possible.
Key Installation Practice #6
Do not loop or connect the decoder cable back to the controller board circuit. All wire path from the daughter board
will end at a decoder. Communication cables not being used must be capped and water proofed.
500 (152m)
Maximum
500 (152m)
Maximum
500 (152m)
Maximum
Cap all Wire Ends
IMPORTANT!
Do not touch the white and
black wires together.
30’’ (76.2cm)
Minimum
Buried Depth
Surge Arrester
Ground Plate
2008 © The Toro Company • Irrigation Division • www.toro.com Part Number 373-0431 Rev. C