Technical Specifications

PRINSCO GOLDLINE HD PIPE SPECIFICATION
Page 2 of 2
1717 16
th
St NE | 3
rd
Floor | Willmar, MN 56201 | 800.992.1725 | www.prinsco.com
© Prinsco, Inc. 11/09
Installation
Pipe and fittings shall be installed in accordance with ASTM D2321 or ASTM F449 and Prinsco’s
published installation guidelines. Minimum cover for AASHTO H-25 loads shall be 12” to sub-grade in
trafficked areas where flexible pavement is installed and shall be 12” to the surface of rigid pavement.
Contact your local Prinsco representative or visit
www.prinsco.com for the latest installation guidelines.
Reference Specifications
This specification references the latest edition and revisions of the following standard specifications:
ASTM F405 Standard Specification for Corrugated Polyethylene (PE) Pipe and Fittings
ASTM F667 Standard Specification for Large Diameter Corrugated Polyethylene Pipe and
Fittings
ASTM D1248 Standard Specification for Polyethylene Plastics Extrusion Materials for Wire and
Cable
ASTM D3350 Standard Specification for Polyethylene Plastics Pipe and Fittings Materials
ASTM D2321 Standard Practice for Underground Installation of Thermoplastic Pipe for Sewers
and Other Gravity-Flow Applications
ASTM F449 Standard Practice for Subsurface Installation of Corrugated Polyethylene Pipe for
Agricultural Drainage or Water Table Control
ASTM D1056 Standard Specification for Flexible Cellular Materials Sponge or Expanded
Rubber