Warranty
Feature Function List
BWG HJ81
BWG, Heat Jacket Control System, Model: HJ81
The HJ81 is “heat jacket” software. (It turns on the pump to heat; there is no separate heater.)
• Software program: HJ81R1A • Mini bath panel (VL200/240/260)
• 120V GFCI cord connect • 15A power configuration
• Pump & Light status indicator lights
• Digital temperature display – Set Temperature Range 60° F - 104° F, Default 100°F
• Automatic timeouts for each function:
12V Light (on/off): 4 Hrs 120V Pump (on/off): 15 minutes
• Settable filter cycle: Two cycles per day. First starts one minute after start up. Second starts 12 hours
later. Duration is programmable for 0, 30, 60 min. - Default is 30min.
To program, press or , then press Jets to enter program, then press or to adjust, finally press
Jets to exit programming.
• Standby mode press or , then light "Sb"
120V Pump and Light relays will open. Press any key to Cancel Standby mode
• Pump turns On when water temperature is 2° F below set temperature and turns Off when water
temperature is 1°F above set temperature.
• Freeze protection 40° F (Not Functional after High-Limit Protection engages)