Installation Guide
Shower walls may be made waterproof using KERDI/-KERDI-DS or KERDI-BOARD prior to construction of the shower base.  
The waterproofing is carried to the height of the showerhead (at minimum). KERDI or KERDI-BOARD application on ceiling is optional for showers.   
For continuous-use steam rooms, KERDI-DS is applied to walls and ceilings. For intermittent use steam showers, KERDI or KERDI-BOARD is applied to 
walls and ceilings.
20  INSTALLATION — Walls and Ceilings
Walls and Ceilings
Please refer to Schluter
®
-Systems' installation videos in addition to reading the instructions below.
INSTALLATION
Clean any dust or other debris from the 
surface of the solid backing. Dampen 
particularly dry and porous substrates in 
order to help prevent premature drying or 
skinning of the thin-set mortar.
1
Apply unmodified thin-set mortar using a 
1/4" x 3/16" (6 mm x 5 mm) V-notched 
trowel or the KERDI-TROWEL. Embed 
KERDI or KERDI-DS in the mortar and work 
the membrane onto the entire surface to 
ensure full coverage and remove air pockets.
2
Seams in the membrane are constructed 
by overlapping the edges by 2" (50 mm) or 
by abutting adjacent sheets and installing 
KERDI-BAND, centered over the joint.  
Any protrusions through the membrane  
(e.g., mixing valve, shower head, etc.) 
must be sealed with KERDI-SEAL-PS/-MV, 
KERDI-FIX, or other suitable sealant.
3
Schluter
®
-KERDI or Schluter
®
-KERDI-DS over solid backing
Schluter
®
-KERDI-BOARD over wood or metal framing
The thin-set mortar used for bonding KERDI/-KERDI-DS to walls and ceilings must be appropriate for the substrate and must penetrate and engage the 
membrane fleece. For most substrates (e.g., gypsum board or CBU), an unmodified thin-set mortar is used. The mortar must be mixed to a fairly fluid 
consistency, but still able to hold a notch.
KERDI-BOARD can be mounted vertically 
or horizontally on framing with appropriate 
screws and corresponding KERDI-BOARD-ZT 
washers. Minimum board thickness = 1/2" 
(12.5 mm) for studs spaced at 16" (40.6 cm) 
o.c.; 3/4" (19 mm) for studs spaced at 24" 
(61.0 cm) o.c. Screws must reach a depth of 
at least 3/4" (20 mm) in wood studs and at 
least 3/8" (10 mm) in metal studs.
1
Abut panels over the center of the studs.  
Screws may be placed between adjacent 
panels such that the washers fasten both 
panel edges. The maximum allowable 
on-center fastener spacing is 12" (30 cm) 
for walls and 6" (150 mm) for ceilings.
2
KERDI-BOARD joints, corners, and fastener 
penetrations are sealed with KERDI-BAND 
and KERDI-KERECK corners, ensuring 
a minimum 2" (50 mm) overlap. Apply 
unmodified thin-set mortar using a 1/4" x 3/16"  
(6 mm x 5 mm) V-notched trowel or the  
KERDI-TROWEL. Embed KERDI-BAND/-
KERECK in the mortar and work the 
membrane onto the surface to ensure full 
coverage and remove air pockets. Any 
protrusions through the panel (e.g., mixing 
valve, shower head, etc.) must be sealed with 
KERDI-SEAL-PS/-MV, KERDI-FIX, or other 
suitable sealant.
3
Grab bars, wall-mounted toilets, or other heavy objects must be anchored in the structure or solid blocking behind KERDI-BOARD. Installation instructions 
for other applications of KERDI-BOARD (e.g. fully embedded or spot-bonded over solid backing) can be found in the 12.1 Schluter
®
-KERDI-BOARD technical 
data sheet.
KERDI-SEAL-PS/-MV
KERDI-SEAL-PS/-MV










