Third Party Verification Claim

Page 23 of 129 Report No.: JAT2209271146SR-1
UL 859
Clause
Requirement + Test
Result - Remark
Verdict
Room 303, Building 1, No.316, Renzhou Road, Shatian Town, Dongguan City, Guangdong Province, China.
Tel: 0769-81710286 E-mail: wangzhao@junantest.com Website: www.junantest.com
Exception: A length of flexible cord may be used
for external connections between parts of the
appliance if flexibility is essential.
P
16.2
A wireway shall be smooth and entirely free from
sharp edges, burrs, fins, moving part similar
abrading surfaces that might damage the
insulation on the conductors
P
16.3
A hole in a sheet metal wall through which
insulated wires pass shall be provided with a
smooth rounded bushing or shall have a smooth,
well-rounded surface upon which the wires
bear
P
16.4
A separate foot switch provided with an appliance
shall be connected to the appliance by flexible
cord no lighter than Type SJ.
N/A
16.5
Insulated internal wiring (including a grounding
conductor) shall consist of a type or types of wire
that are acceptable for the application with regard
to
N/A
he temperature and voltage to which the wiring is
likely to be subjected
N/A
Exception: Insulated internal wiring evaluated as
an uninsulated live part is not required to comply
with the criteria specified in (a) (d)
N/A
16.6
Internal wiring composed of insulated conductors
shall comply with the Standard for Appliance
Wiring Material, UL 758.
Internal wire have approved
UL
P
Exception No. 1: Insulated conductors need not
comply with UL 758 if they comply with one of
the following
N/A
The Standard for Thermoset-Insulated Wires and
Cables, UL 44
The Standard for Thermoplastic-Insulated Wires
and Cables, UL 83
N/A
16.7
A splice and connection shall be mechanically
secure and shall provide effective electrical
contact
N/A
16.8
Aluminum conductors, insulated or uninsulated,
used as internal wiring, such as for interconnection
between current-carrying parts or as motor
windings, shall be terminated at each end by a
method acceptable for the combination of metals
involved at the connection point
P
16.9
If a wire-binding screw construction or a pressure
wire connector is used as a terminating device for
aluminum, it shall be required for use with
aluminum under the conditions involved (for
example, temperature, heat cycling, vibration
N/A
16.10
A soldered connection shall be made mechanically
secure before being soldered if breaking or
loosening of the connection results in a risk of fire,
electric shock, or injury to persons
N/A