Datasheet

Fan Model :
FD128020LB(2F3)
Test Date :
2001/05/14
Key Point :
FD128020LB(2F3)
Order No. :
8020-14
Blade No. : 7 Test No. :
YS
Motor Poles : 4 Method :
Constant Voltage
Rating Voltage(V) : 12 VDC Tunnel Setup : Inlet Chamber Type
Rating Current(A) : 0.06
Temperature() : 27
R.H.(%) :
86
Rating Speed(rpm) : 2100 Barometric Pressure(mmHg) : 756.6
Test Voltage(V) : 12 VDC Acoustic ( dB(A)/1M ):24.0dB(A)
Max. Flow rate(CFM) : 25.060 Mea. Distance(M): 1
Max. Flow rate(m
3
/min) :
0.709
Background Noise:10.0dB(A)
Max. Pressure(in-H
2
O) :
0.061
Vibration Level (mm/sec
2
): N / A
Max. Pressure(mm-H
2
O)
:
1.542 Remark:
Voltage Current Power Speed
CFM m3/min in-H2O mm-H2O V A W rpm
1 25.060 0.7094 0.0000 0.000 12.00 0.054 0.65 2029
2 18.786 0.5318 0.0205 0.521 12.00 0.055 0.66 1940
3 12.510 0.3542 0.0294 0.747 12.00 0.054 0.65 1999
4 6.248 0.1769 0.0444 1.128 12.00 0.056 0.67 1833
5 0.000 0.0000 0.0607 1.542 12.00 0.057 0.69 1703
Examiner: Tester:
1
Fan Performance Curve
Yen Sun Technology Corp.
Fan Performance Test Report
Curve Pts
Flowrate Static Pressure
Approver:
劉智光 許志聰 張馥怡
0.0000
0.0200
0.0400
0.0600
0.0800
0.000 7.500 15.000 22.500 30.000
Flow Rate (CFM)
Static Pressure (inH2O)
FD128020LB(2F3)