Chapter 12: Troubleshooting
Flow Sensor Reading Always Zero (continued)
from
previous page
Is
debris impeding
sensor movement?
Yes
Remove debris.
Reinsert sensor.
Connect wires.
Retest.
Insure all water is off.
Drain line to
relieve pressure.
Remove sensor insert.
Replace defective sensor.
No
EV-CAB-SEN is
defective.
See Appendix G
for measuring
continuity.
Is there
12+ VDC measured
at black and white
EV-CAB-SEN
wires?
Yes
No
Disconnect the
EV-CAB-SEN wires
from the flow sensor
red and black wires.