DXi User Manual
Chapter 4: Setup
Learn Flow/Current
For the DXi controller to issue meaningful alerts when there is a flow or current
problem, the proper flow and current rates must be “learned” by the system. The
Learn Flow/Current command therefore teaches the DXi system the nominal (ideal)
current and flow settings to each valve and station. One would typically activate the
Learn command for either a new system or when a when a new flow meter has been
installed.
The Learn Flow/Current command consists of three screens:
Current %'s: Setup the Nominal Current limits. Use the Control Dial to switch
between and adjust the Upper and Lower Limit fields. Recommended value for Upper
Limit and Lower Limit is 30% for both.
Flow %'s: Setup the Nominal Flow limits. Use the Control Dial to switch between
and adjust the Upper and Lower Limit fields. Recommended value for Upper Limit
and Lower Limit is 20% for both.
Use the Control Dial to activate the Learn Flow/Current command, triggering the
3rd screen above.
If the “All Satellites” check box is checked, the learn function will be
performed on the submaster and all connected satellites.
Start Now All Satellites
Delay Learn Until