Chapter 12: Troubleshooting
Station / Valve Does Not Water (continued)
from
previous page
Field wiring and solenoid
good. Now test electrical
output.
Electrical ouput good.
Does irrigation
commence for the known
working station?
Does
irrigation commence
for the suspect
working station?
If station alerts are raised,
react as necessary.
Verify integrity of field wiring
from output board to
solenoid and repair / replace
if faulty.
If field wiring is OK, replace
valve / solenoid for the
defective zone.
If station alerts are raised,
react as necessary.
If you suspect faulty
electrical output, contact
Rain Master technical
support.
No
No
Yes
Yes
Manually operate the known
working station output that is
wired with the suspect
defective station wires for
one minute.
Manually operate the suspect
station output that is wired to
the known good station for
one minute.