Manual
Routine Inspections Checklist
■ Turn on each zone for ve to 10 minutes and walk the area, looking
for excessively wet areas that might indicate leaks.
■ Inspect air/vacuum relief valves (subsurface installations only) and
automatic ush caps for proper operation.
■ Check pressures at the supply manifold and ush ends of each zone,
and compare them with the base information on the System Data
Record. For proper ushing, the ush-end pressure should be at least
10 PSI.
■ Check the operational ow of each zone and compare it with the
design ows or the ows on the System Data Record. High ows
could indicate leaks or malfunctioning automatic ush caps. Flows
lower than expected could indicate clogged drippers, drippers with
excessive salt build-up, kinked dripline or a clogged lter. Low ows
might also indicate that the capacity of the installed remote control
valves, lters or pressure regulators are too low, thus restricting the
ow to the zone.
Component Maintenance Checklists
Remote Control Valves
■ Upon initial inspection, check to see if the valve is properly sized for
the zone ow. Refer to the manufacturer’s specication. Oversized
valves may not close properly and undersized valves will restrict ow
and cause excessive pressure loss.
■ Follow the manufacturer’s recommended procedures for repair and
general maintenance.
■ Inspect for proper operation when opening or closing. A weeping
valve can cause excessively wet areas at low points in the zone.
Landscape Dripline Design _____________________________________________________________
■ Routine Preventative Maintenance
NOTES:
36