Third Party Verification Claim

Mr. John Ruprecht Clear View Glass Railings
AET Project No. 05-20608
March 2, 2021
Page 3 of 3
borne debris would not penetrate the enclosure and its structural elements. Therefore, this test is not
required for the panels used as a guardrail system.
Summary
Based on our understanding of the NCBC requirements, our conclusions follow:
1. Each panel is constructed of fully tempered, laminated glass.
2. Each panel is secured to the structure with three supports.
3. A top rail is not required for these panels.
4. Wind pressure previous testing confirms that the panels meet the 180 mph factored wind
speed requirement, with a calculated factor-of-safety of 2.24.
5. The panels do not require wind debris projectile testing.
Please call or e-mail us to discuss this analysis or any portion of the project to evaluate your panels.
Sincerely,
American Engineering Testing, Inc.
Chris Hartnett, PE*
Principal Engineer
*MN, WI
Phone: 651-647-2750
chartnett@amengtest.com
Attachment: Testing and Code Evaluation
1: North Carolina Figure 1609.1 Ultimate Wind Design Speed.
2: ASCE 7-10 Wind & Pressure Calculations.
3. Finite Element Modelling.
4: Physical Testing