Third Party Verification Claim
Mr. John Ruprecht – Clear View Glass Railings 
AET Project No. 05-20608 
March 2, 2021 
Page 3 of 3 
borne debris would not penetrate the enclosure and its structural elements. Therefore, this test is not 
required for the panels used as a guardrail system.  
Summary 
Based on our understanding of the NCBC requirements, our conclusions follow: 
1.  Each panel is constructed of fully tempered, laminated glass.  
2.  Each panel is secured to the structure with three supports. 
3.  A top rail is not required for these panels. 
4.  Wind pressure – previous testing confirms that the panels meet the 180 mph factored wind 
speed requirement, with a calculated factor-of-safety of 2.24. 
5.  The panels do not require wind debris projectile testing. 
Please call or e-mail us to discuss this analysis or any portion of the project to evaluate your panels. 
Sincerely, 
American Engineering Testing, Inc. 
Chris Hartnett, PE*             
Principal Engineer 
*MN, WI             
Phone: 651-647-2750 
chartnett@amengtest.com 
Attachment: Testing and Code Evaluation 
    1: North Carolina Figure 1609.1 – Ultimate Wind Design Speed. 
     2: ASCE 7-10 Wind & Pressure Calculations. 
    3. Finite Element Modelling. 
    4: Physical Testing 