Installation Guide

40
© 2021 United States Stove Company
the tap is completely sealed. Manometer should
read no pressure.
MANIFOLD PRESSURE TEST
1. Light pilot.
2. Loosen manifold (OUT) pressure tap by turning
screw counter-clockwise (see (B).
3. Attach manometer to pressure tap using a 1/4”
(6 mm) I.D. hose.
4. Light burner. Check manometer reading.
5. Turn burner and pilot off.
6. Disconnect manometer hose and tighten the
manifold (OUT) pressure tap by turning screw
clockwise. Screw should be snug. Do not over
tighten.
7. Attach the manometer to the manifold pressure
tap (B) to verify it is completely sealed. The
manometer should read no pressure when pilot
and burner are on.
Inlet Pressure Tap (A)
Natural Propane (LP)
Gas
Supply
MIN
5.0” WC
(1.25 KPA)
12” WC
(2.74 kPa)
MAX
10.5” WC
(2.61 kPa)
14” WC
(3.49 kPa)
Manifold Pressure Tap (B)
Natural Propane (LP)
Gas
Supply
Normal
3.8” WC
(0.95 kPa)
11.0” WC
(2.74 kPa)
BURNER FLAME ADJUSTMENTS
WARNING::
TO AVOID PROPERTY DAMAGE OR
PERSONAL INJURY, ALLOW AMPLE TIME TO
COOL BEFORE MAKING ANY ADJUSTMENTS.
VENTURI ADJUSTMENT MUST BE DONE BY
A QUALIFIED SERVICE TECHNICIAN.
Burner ame appearance and characteristics
are affected by altitude, fuel quality, venting
conguration, and other factors. After installation,
additional adjustments may be required to achieve
optimum ame appearance and visual aesthetics.
GAS FLAME ADJUSTMENT
During the initial installation, the air shutter opening
should be checked to be certain that the shutter
is set correctly as specied below. Adjustments
should only be made by a qualied installer. NOTE:
For altitudes above 5,000 ft., some variations may
be required.
Be sure burner and logs are properly installed. After
burner has been properly installed and operated
for 2-3 hours, small additional adjustments to
the air shutter may be necessary for nal ame
appearance. These small shutter adjustments can
be made by the following procedure. NOTE: Very
small changes in shutter settings make major
changes in ame appearance.
1. The air shutter control is located below the
cover panel at the right center of the appliance
next to the valve assembly.
2. If ame is too “blue,” push the air shutter control
in (open) in small 1/8” increments until ame
turns desired realistic “orange” color.
3. If ame is too “orange” or is causing sooting on
viewing glass, pull the air shutter control out
(close) in approximately 1/8” increments until
sooting stops.
CAUTION:
TRY EACH NEW SHUTTER SETTING
APPROXIMATELY 1 HOUR BEFORE MAKING
ADDITIONAL CHANGES. CHANGES IN BURNER
FLAME CAN BE MADE BY RE-ARRANGING THE
MEDIA.
Air Shutter
Control
Factory Set Venturi Openings
Fuel Air Shutter Opening
Natural Gas Closed
LP Gas Closed
OPERATING INSTRUCTIONS