Third Party Verification Claim

AIR FILTER TESTING LABORATORIES, INC.
4632 Old LaGrange Road • Buckner, Kentucky 40010
Phone (502) 222-5720 • Fax (502) 222-9881
ASHRAE STANDARD METHOD 52.1-1992 AIRFLOW -vs- INITIAL RESISTANCE
AND INITIAL POLLEN REMOVAL EFFICIENCY; CLEAN DEVICE
DEVICE TESTED
Test Requested By
REP INDUSTRIES, INC.
Manufacturer
REP INDUSTRIES, INC.
Test Sample Procurement
FURNISHED BY MANUFACTURER
REPORT NO. Product Name
SAFE-GARD AIR-IN FILTRATOR
14135 Model No.
1144
Dimensions
11.00 IN. H X 25.00 IN. W X 2.00 IN. D (NOMINAL)
TEST NO.
Product Description
MEDIA TYPE - SYNTHETIC W/ CARBON
1
SHEET NO.
1
TEST CONDITIONS
Test Airflow Rate
161
ft³/min (cfm)
Initial Resistance
0.08
in. w.g.
Test Pollen / Size
GIANT RAGWEED / 17 - 19 µm
Test Pollen Increment
10
g
TEST RESULTS - see attached performance curves
Initial Pollen Removal Efficiency
96.3
%
PERFORMANCE CURVES
DATE
10-22-2014
TEST SUPERVISOR
M.A.M.
ADMINISTRATIVE
APPROVAL
0.04
0.06
0.08
0.12
0 81 121 161 201
Airflow Rate - ft³/min (cfm)
0
0.2
0.4
0.6
0.8
1
Resistance - in. w.g.
CLEAN DEVICE
Airflow -vs- Initial Resistance
I
N D EPEN DEN T
C
ER TIFICA TION
AFT L, I
N C
.
EST
. 1970

Summary of content (1 pages)