Use and Care Manual
INSTALLATION MANUAL---Installation of the outdoor unit 
The air and humidity left inside the refrigerant circulat-
ion can cause compressor malfunction. After having co-
nnected the indoor and outdoor units, bleed the air and 
humidity from the refrigerant circulation using a va-
cuum pump. 
Refrigerant flow direction
2-way valve
(6) Open 1/4 turn
valve cap
(1) Turn
(8) Tighten
(2) Turn
3-way valve
(8) Tighten
(1) Turn
(7) Turn to fully
 open the valve
(7) Turn to fully 
 open the valve
(8) Tighten
Service 
port nut
Valve cap
(1) Unscrew and remove the caps from the 2 - way and 
 3-way valves. 
(2) Unscrew and remove the cap from the service port.
(3) Connect the vacuum pump hose to the service port.
(4) Operate the vacuum pump for 10 - 15 minutes until 
 an absolute vacuum of 10 mm Hg has been reached. 
(5) With the vacuum pump still in operation , close the 
 low - pressure knob on the vacuum pump coupling. 
 Stop the vacuum pump. 
(6) Open the 2 - way valve by 1/4 turn and then close it 
 after10 seconds. Check all the joints for leaks using 
 liquid soap or an electronic leak device. 
(7) Turn the body of the 2-way and 3-way valves. 
 Disconnect the vacuum pump hose. 
(8) Replace and tighten all the caps on the valves. 
3-way valve diagram
connect to indoor unit
open position
spindle
service port cap
Connect to 
outdoor unit
Valve core
needle
INSTALLATION MANUAL--- final stages 
wall
(indoor) (outdoor)
piping
piping
gasket
insulating tape
insulating covering
Clamps
1. Wind insulating covering around the joints of the ind-
 oor unit and fix it with insulating tape.
2. Fix the exceeding part of the signal cable to the 
 piping or to the outdoor unit.
3. Fix the piping to the wall ( after having coated it with
 insulating tape) using clamps or insert them into pla-
 stic slots.
4. Seal the hole in the wall through which the piping is
 passed so that no air or water can fill.
 Do the ON/OFF and FAN operate normally?
 Does the MODE operate normally?
 Do the set point and TIMER function properly?
 Does each lamp light normally?
 Do the flap for air flow direction operate normally?
 Is the condensed water drained regularly? 
 Is there any abnormal noise or vibration during 
 operation?
 Could the noise , the air flow or the condensed water 
 drainage disturb the neighbours?
 Is there any coolant leakage?
Indoor unit test
Outdoor unit test
Note: the electronic controller allows the compressor to 
 start only three minutes after voltage has reached 
 the system.
20
BLEEDING
Indoor unit