Instructions / Assembly
Page 4 of 11 Revised: 2016-05-17
3. Technical Installation Instructions
3.1 General Information
CAUTION!
These tanks must be installed in accordance with these instructions and in accordance with CAN/CSA-
B139, Installation Code for Oil-Burning Equipment (Canada) or NFPA-31, Standard for the Installation of
Oil-Burner Fuels and Other combustible Liquids (USA) and in compliance with any applicable local codes
or regulations.
Do not transfer oil from the old tank into this tank.
3.2 Handling instructions
In order to avoid damage to the tank, it shall be protected from impact, fall or abrasion during loading,
transporting, unloading and intermediate storage.
3.3 Inspection of Tank and Contents
3.3.1 Unpacking and Damage Evaluation
• Any protective packaging supplied by the manufacturer shall not be removed prior to delivery at
the installation location.
• After unpacking, each tank shall be visually inspected for “unacceptable” damage of the support,
closed secondary containment/dike, primary tank, fittings and accessories included with the tank.
“Unacceptable” is defined as any material, component or product defects such as cuts, holes or
permanent deformation of structural or fluid confining parts which could cause leakage, excessive
corrosion, or other mechanical and fire safety hazards. Minor deformation and dents are
acceptable except at the closed secondary containment/dike seam.
If damage is found and the damage could result in leakage or could reduce the stability of the tank on the
ground, IT SHALL NOT BE INSTALLED.
Be sure to use care when you cut the shrink-wrap and remove the packing material. All packing
materials should be disposed of properly.