Specification

Dimensions TempControl Mixing Valve, 7-900A and 7-1000A
Physical Dimensions
Model No. A B C D E F
7-900A
22 3/4"
(578mm)
2 11/16"
(68mm)
11 1/2"
(296mm)
2 9/16"
(65mm)
2 9/16"
(65mm)
11 3/8"
(289mm)
7-1000A
22 3/4
(578mm)
2 11/16
(68mm)
11 1/2
(296mm)
2 9/16
(65mm)
2 9/16”
(65mm)
11 3/8”
(289mm)
Flow Rate - gpm (L/min)
Valve Model Min. Flow Rate* Min. Flow Rate
Pressure Differential - psi (kPa)
5 psi
(34 kPa)
10 psi
(69 kPa)
20 psi
(138 kPa)
25 psi
(172 kPa)
30 psi
(207 kPa)
45 psi
(310 kPa)
7-900A
0.5 gpm
(1.9 L/min)
13 gpm
(49 L/min)
30 gpm
(114 L/min)
55 gpm
(209 L/min)
76 gpm
(288 L/min)
84 gpm
(318 L/min)
89 gpm
(337 L/min)
104 gpm
(394 L/min)
7-1000A
0.5 gpm
(1.9 L/min)
13 gpm
(49 L/min)
38 gpm
(144 L/min)
67 gpm
(254 L/min)
100 gpm
(379 L/min)
111 gpm
(421 L/min)
120 gpm
(455 L/min)
140 gpm
(531 L/min)
*Minimum ow rate when valve is installed at or near the hot water source with recirculated tempered water and continuously operating circulating
pump.
Symmons Industries, Inc. 31 Brooks Drive Braintree, MA 02184 Phone: (800) 796-6667 Fax: (800) 961-9621
Copyright © 2016 Symmons Industries, Inc. symmons.com gethelp@symmons.com ZV-1164 REV E 052316