Installation Guide
26
Installation Practices
is not supported independent of the building structure or gas piping system, HOME-FLEX® 
tubing cannot be used to connect directly to the meter.
Connection by Special Termination Fitting
Do not use HOME-FLEX® CSST as a direct connection if the meter must be supported by the 
piping system. If the meter is supported by the building structure, common practice is to 
route the CSST system to a termination ange mounted to the exterior of the building, and 
to connect the meter to the termination ange with rigid pipe. Alternatively, rigid pipe can 
be used to penetrate the building, with an attachment to HOME-FLEX® inside the structure. 
(Figure 4.14)
Direct Connection
If a direct connection from HOME-FLEX® to an independently supported gas meter is permit-
ted by the local utility, the connection should include an extra 3-6" of length to allow for 
building settling and meter movement. Exposed sections of CSST are to be wrapped with 
self-bonding silicone tape, especially if the building is of masonry construction. For direct 
connections through masonry construction, a PVC sleeve is required, and also recommended 
for wood frame construction. (Figure 4.15)
Note: Check with the local servicing utility prior to directly connecting HOME-FLEX® to the 
gas meter as utilities regulate connections to meter attachments.
4.6  Appliance connections
Termination Fittings with Appliance Connectors
The HOME-FLEX® termination ange tting is designed to service moveable appliances and 
quick-connect devices at oor and hallow wall piping outlets (Figure 4.16) in combination 
with a HOME-FLEX® Flexible Appliance Connector or similar approved device. The termina-
tion outlet minimizes the need 
for concealed ttings and makes 
the installation of gas connec-
tions for moveable appliances 
easy. The ange plate should be 
securely fastened in place during 
rough-in of the structure. It may 
be attached to a brace spanning 
between wall studs or directly to 
the oor.
As an alternative to the special 
termination ange, a termination 
Figure 4.14  Connection to Building supported Meter
Sleeve 
(if required)
Sealant 
(typical)
Termination 
Fitting
Service Line
Meter
House Service 
Regulator
Note: Diameter of hole shall 
be at least 1/2" greater 
than OD of tubing nad shall 
be sleeved in accordance 
with local building code (if 
applicable).
Figure 4.15  Independently Supported Meter
Sealing 
Radius of 3-6"
Figure 4.16  HOME-FLEX® Connection to Moveable Gas Appliance
Moveable 
Appliance
Shut-off 
Valve
Termination 
Fitting
Flexible Protec-
tive Conduit
Mounting 
Brace
HOME-FLEX
®
Appliance 
Connector