Installation Guide
22
Installation Practices
Holes and Cuts in Top and Sole Plates
Holes bored through top plates, top frame mem-
bers and sole plates should not exceed 50% of 
the width of the structure, and should be in the 
center of the structure. If a sole or plate is to be 
cut for the routing of HOME-FLEX® tubing, the 
width of the cut should be ½" greater than the 
outside diameter of the tubing and no greater 
than 2 inches. Tubing must be protected with 
striker plates in accordance with Section 4.4. (See 
Figure 4.3) 
Routing through vertical wall framing
Requirements for boring through vertical mem-
bers of wall framing dier depending on whether 
the member is bearing or not. For non-bearing 
members (Figure 4.4), the size of the hole should be no larger than 60% of the width of the 
member. For bearing members, the size of such hole should be no more than 40% of the 
member. (Figure 4.5) 
Routing through metallic surfaces
When installing HOME-FLEX® through galvanized steel studs, plastic grommets (often sup-
plied by the stud manufacturer) should be used to reduce potential damage to the yellow 
jacket of the HOME-FLEX® tubing. When installing through holes in other metallic members, 
the tubing must be similarly protected from contact with the member to prevent mechani-
cal wear on the yellow jacket and tubing. Acceptable means of protection include: rubber 
grommets, bushings, HOME-FLEX® Flexible Protective Conduit, PVC tape, thermal contraction 
sleeve material, or a minimum of four wraps of 10 mil duct tape.
Concealed Locations for Fittings
The HOME-FLEX® mechanical attachment ttings have been tested and are listed per the 
requirements of ANSI LC1 and CSA 6.26 Standard (USA and Canada). This specication pro-
vides test requirements which certify ttings for concealed installations and connections to 
appliances where concealing the ttings is the only practical alternative
These guidelines address some of the known situations which may require the use of a con-
cealed tting. While accessibility of ttings is always preferred, there are some situations 
where concealing the ttings is the only practical option. This guide cannot address all appli-
cations of concealed ttings, but instead provides general instructions to demonstrate the 
principles which apply to ttings listed for installation in concealed locations (National Fuel 
Gas Code, NFPA 54 Chapter 7).
Figure 4.3  Holes and Cuts in Top and Sole Plates
2x4
2x4
Stud
Top Plate
Sole Plate
2” Max. 
Cut Width
W
Hole for Tubing
W/2 Max
W/2
W/2
Figure 4.4  Holes in Non-Bearing Walls
2x4
Holes up to 60% 
of Stud Width
Non-bearing Wall
2
1
⁄8" 
Max
3
1
⁄2"
1
1
⁄2"
5
⁄8" 
Max
Figure 4.5  Holes in Bearing Walls
2x4
Non-bearing Wall
Holes up to 40% 
of Stud Width
1
3
⁄8" 
Max
3
1
⁄2"
1
1
⁄2"
1" 
Max










